Lennox Hearth ELITE VINT-DVS-U User Manual

Page 13

Advertising
background image

13

Vent Parts List

Secure Vent direct­vent pipe by Security Chimneys* may be used with
this appliance. Please see the lists below to verify the components avail­
able from each direct­vent pipe manufacturer. Snorkel terminations are
available for applications which may require vertical rise on the building
exterior. The components listed below come in a galvanized finish. Most
of the components are also available in a painted black finish. Add a “B”
to the end of the part number when ordering if a black part is desired.

Security™ Secure Vent 6-5/8”x 4” Pipe

Part Number

Description

SV4LC

6” Pipe Length

SV4L12

12” Pipe Length

SV4L24

24” Pipe Length

SV4L36

36” Pipe Length

SV4L48

48” Pipe Length

SV4LA

6” Pipe, Adjustable

SV4LA12 12” Pipe, Adjustable

SV4FA

Flashing, 1/12 to 6/12 Roof Pitch

SV4FB

Flashing, 7/12 to 12/12 Roof Pitch

SV4RSM

Wall Radiation Shield

SV4E46

45º Elbow

SV4E90

90º Elbow

SV4VS

Vinyl Shield Protector

SV4FC

Storm Collar

SV4CGV

Vertical Termination Cap

SV4BF

Firestop

SV4CHC

Horizontal Termination Cap

SV4STC36

Snorkel Termination Cap (36”)

SV4STC14

Snorkel Termination Cap (14”)

SV4BM

Wall Band

Simpson Dura­Vent GS 6­5/8”x 4” Pipe

Part Number

Description

908

6” Pipe Length

907

9” Pipe Length

906

12” Pipe Length

904

24” Pipe Length

903

36” Pipe Length

902

48” Pipe Length

911

11” to 14­5/8” Pipe, Adjustable

942

Wall Thimble

940

Rnd Support Box/Wall Thimble Cover

941

Cathedral Ceiling Support Box

943

Flashing, 0/12 to 6/12 Roof Pitch

943S

Flashing, 7/12 to 12/12 Roof Pitch

945

45º Elbow

990

90º Elbow

950

Vinyl Siding Standoff

953

Storm Collar

963

Ceiling Firestop

988

Wall Strap

981

Snorkel Termination (36”)

982

Snorkel Termination (14”)

984

Horizontal Termination Cap

985

Horizontal Termination Cap (High Wind)

980

Vertical Termination Cap

991

Vertical Termination Cap (High Wind)

Horizontal Vent Installation
Venting terminals may not be recessed into a wall or siding.

1. Set the unit in the desired location. Check whether or not wall studs

are in the way when the venting system is attached. If wall studs are
in the way, you may want to adjust the location of the unit.

2. Any stove that is horizontally terminated and has a vertical section

of pipe off the top of the stove, that first section of pipe must be a
minimum of 18” long.

3. All horizontally terminated vent installations may only use 6­5/8”x 4”

Security™ Secure Vent pipe*.

4. Assemble the desired combination of pipe and elbow(s) to the appli­

ance adapter with pipe seams facing down. Offsetting the pipe seams
as double seams in one place will cause the outer pipe to take an oval
shape.

5. When this pipe passes through a wall, a wall thimble ­ Simpson #942

or Security™ #SV4RSM ­ is required. The hole in the wall for the
wall thimble should be 9­1/4”x 10­1/4”. If the wall being penetrated
is constructed of non­combustible material (i.e. masonry block or
concrete), a 7” diameter hole is acceptable and a wall thimble is not
required.

6. Horizontal runs of vent pipe must be supported every 3 feet. Wall

straps ­ Simpson #988 or Security™ #SV4BM ­ are available for this
purpose.

7. If the vent passes through a ceiling or floor, a firestop ­ Simpson #963

or Security™ #SV4BF ­ is required.

8. Also note that venting terminals shall not be recessed into a wall or

siding. If installing the termination cap on a wall covered with vinyl
siding, a vinyl siding standoff ­ Simpson #950 or Security™ #SV4VS
­ or furring strips must be used to ensure that the termination cap is
not recessed into the siding.

9. The horizontal run of vent should have a 1/4” rise for every 12” of run

toward the termination. Never allow the vent to run downward. This
could cause high temperatures and may present the possibility of a
fire.

10.If the wall being penetrated is constructed of noncombustible material,

such as masonry block or concrete, an 7” diameter hole is acceptable
and a wall thimble is not required..

11. The location of the horizontal vent termination on an exterior wall must

meet all local and national building codes and must not be blocked
or obstructed. For allowable external vent termination locations (see
Page 17).

12. Allowable clearances from the vent pipe to combustible materials must

be maintained. See Page 9 for these clearances.

13. Do not locate the termination cap where it may be blocked by shrub­

bery or snow.

* Other approved chimney brand is Simpson Dura­Vent DV­GS.