2 liebert nx ups to non-liebert nx ups, Figure 5 connecting a liebert nx to a non-nx ups, Table 1 human interface-indicators and switches – Liebert Extender/Adapter User Manual

Page 7: Table 2 electrical rating, Table 3 part number description, Liebert nx ups to non-liebert nx ups, Figure 5, Connecting a liebert nx to a non-nx ups, Table 1, Human interface—indicators and switches

Advertising
background image

Installation

3

2.2

Liebert NX UPS to Non-Liebert NX UPS

1. Connect the power cables of the adapter to the Phase A, Neutral and Ground Output of each UPS.
2. Connect the LBS cable to COM1 of the LBS Signal Adapter connected to the Liebert NX.
3. Connect the other end of the LBS cable to X4 on the parallel board (UHW241M3) in the NX UPS.
4. Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal

Adapter.

5. The switches of LBS signal adapters connected to the Liebert NX should be in the right position

and the switches of LBS signal adapters connected to the non-NX UPS should be in the left

position (see Figure 5).

Figure 5

Connecting a Liebert NX to a non-NX UPS

!

WARNING

Installation by qualified electrical personnel only—hazardous voltage may be present at the

UPS output connectors.

Table 1

Human interface—indicators and switches

Item

Description

Power port

Connect to Phase A, Neutral and Ground of output of UPS.

LED1 (red)

Power LED. It illuminates when the power is on, turns off when the power fails.

COM1

LBS Signal interface.
Connect to NX series UPS unit.

COM2

RS485 interface.
Connect to other Signal Adapter.
Green LED: Communication Power is OK.
Yellow LED: Adapter is connected to Non NX series UPS.

SWITCH

Switch to left: Connect to Non-NX series UPS unit.
Switch to right: Connect to NX series UPS unit.

Table 2

Electrical rating

Description

Rating

Voltage

120V-277VAC

Frequency

45-65HZ

Current

0.2A Max

Table 3

Part number description

Description

Part Number

150 Meter Kit

NX150MLBSKIT

50 Meter Kit

NX050MLBSKIT

COM1

COM2 SWITCH

COM1

COM2 SWITCH

Power ON

LED1

Power ON

LED1

Power Cable

Connect to NX UPS

LBS

Cable

Power Cable

Connect to non-NX UPS

Communication Cable

up to 492 ft. (150m)