LST IR2 16581 User Manual

LST Safety

Advertising
background image

0832–CPD–0821

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

IR2-16581_DBL_LST_EN_0850.PDF • PAGE 1

A

Building Safety. Building Security.

• Dual infrared sensor

according to EN 54-10, Class 1

• Detection of open fl ames through

fl ickering infrared radiation

• High immunity to deceptive alarms
• Selectable response delay
• Relay contacts for alarm and fault
• Integrated optical test function

Description

The Flame Detector 16581 responds to the fl ickering

infrared radiation of open fl ames. Therefore, it is extre-

mely well suitable for the detection of fi res which are

diffi cult to detect with common smoke detectors – for

example, alcoholic fi res or gas fl ames.

The detector is ideal for the following applications:

• Aviation and automotive industry

• Paint shops

• Warehouses

• Textile industry

• Waste treatment

With two independent infrared sensors for different

wavelengths and with an intelligent evaluation logic, the

detector can safely distinguish between alarm situati-

ons and deceptive alarms. Therefore, it is very insensiti-

ve to disturbance sources such as sunlight, fl uorescent

lamps or electric arcs.

The detector complies with EN 54-10, Class 1, which

means it is suitable to detect fl ames up to a distance

of 25m.

The response delay of the detector can be selected in

4 steps between 1 and 8s. An alarm and a fault conditi-

on is signalled via two dry relay contacts. Conventional

technology is used for alarm transmission to the fi re

detection control panel. The detector can be integra-

ted into an ADM loop by means of a conventional zone

module.

A simple test of the detector can be carried out by

means of the integrated optical self test function, which

does not require additional tools. During this self test,

a built-in infrared source simulates a fi re situation which

activates the detector.

The detector has been designed for indoor use. The op-

tional Detector Mounting Bracket 7127 allows stepless

horizontal and vertical adjustment for the easy adaptati-

on of the detector to the required monitoring area.

For use in explosion-hazardous areas, an Ex version of

the fl ame detector is available on request.

Advertising