Building Safety. Building Security.

Description

The addressable Optical Filtrex Smoke Detector FTX-P1

uses the scattered light principle and was developed

for the detection of smoke particles in heavily conta-

minated areas. The detector is used, for example, in

industrial plants where dust is released by production

or cleaning.

By means of an integrated fan, air samples are drawn

into the sensing chamber through two separate fi lters.

The fan is powered by a separate 24VDC supply and

operates in a 15% duty cycle (5 seconds on, 30 se-

conds off), thus allowing low power consumption as

well as precise evaluation of the air samples.

The fi lters are monitored for contamination. They are

designed to let smoke reach the sensing chamber,

whereas causes of deceptive alarms (dust particles

and tiny drops of water) are kept away from it. The ou-

ter fi lter is removeable and can be cleaned or replaced

by the operator. The modern design of the sensing

chamber allows to reliably evaluate the characteristics

of fi re.

The proven ADM loop technology with System Sen-

sor/200 protocol establishes a permanent communi-

cation between the fi re detection control panel and the

detector. That ensures a periodical function testing of

the detector. In the control panel all types of fi res are

detected by continuously comparing fi re patterns.

Intelligent evaluation algorithms use the current condi-

tion of the sensing chamber to predict the likely time

of the next maintenance. Thus the alarm threshold is

automatically adjusted within the permissible range,

depending on the contamination. With that, the con-

stant response sensitivity of the detector is ensured

for the duration of its usage.

The two LEDs with 360° visibility indicate the activated

condition of the detector. The detector address is se-

lected with two decadic rotary switches, thus allowing

to change the detector without additional tools.

A detector function test can be conveniently conducted

using a magnet or test gas. The detector is attached to

the base B524FTXE.

• ADM loop technology with

System Sensor/200 protocol

• For use in heavily contaminated

areas

• Replaceable fi lter
• Constant response sensitivity
• Function testable with magnet