1 calculating refrigerant charge—example, Table 10 calculating refrigerant charge—example, Table 11 worksheet to calculate refrigerant charge – Liebert Extreme Density Chiller XDC User Manual

Page 27: Calculating refrigerant charge—example, Table 9, Table 10, Table 11, Worksheet to calculate refrigerant charge, 1 - calculating refrigerant charge, Example

Advertising
background image

Piping and Filling with Refrigerant: R-134a and R-407c Circuits

21

2.5.1 Calculating Refrigerant Charge—Example

Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert

XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant

required for one system combining a Liebert XDC with Liebert XD cooling modules (Liebert XD Cool-

Frame, Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDC

with 20 Liebert XDV8 cooling modules.

Table 9

R-134a refrigerant charge for Liebert XD Flex Pipe connector lines to and from any
model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF

Refrigerant Charge,

lb. (kg)

Metal Liebert XD Flex Pipe Connector Length

Supply Line Diameter 1/2"

0.3 lb. (0.14)

4 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

0.5 lb. (0.23)

6 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

0.7 lb. (0.32)

8 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

0.8 lb. (0.36)

10 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

Return Line Diameter 5/8"

0.01 lb. (0.01)

4 ft. Liebert XD Flex Pipe existing Liebert XDV systems

0.02 lb. (0.01)

6 ft. Liebert XD Flex Pipe existing Liebert XDV systems

0.03 lb. (0.01)

8 ft. Liebert XD Flex Pipe existing Liebert XDV systems

0.03 lb. (0.01)

10 ft. Liebert XD Flex Pipe existing Liebert XDV systems

Return Line Diameter 1"

0.13 lb. (0.06)

4 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

0.2 lb. (0.096)

6 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

0.27 lb. (0.126)

8 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

0.33 lb. (0.15)

10 ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply

Table 10

Calculating refrigerant charge—example

Components

Number of Units

or Piping Length,

feet

Pounds

Per Component

Total, lb.

Liebert XDC

1

157

157

Liebert XDV8 Cooling Modules

20

2.32

46.4

Supply Main, 1-1/8"

100

0.45

45

Return Main, 2-1/8"

100

0.28

28

Liebert XDV 1/2" supply Liebert XD Flex Pipes

20

0.8

16

Liebert XDV 5/8" return Liebert XD Flex Pipes

20

0.03

0.6

Total

293

Table 11

Worksheet to calculate refrigerant charge

Components

Number of Units

or Piping Length

Pounds

Per Component

Total

Total