Lgm module driver, Parameter page – Liebert 232 User Manual

Page 15

Advertising
background image

© 1996-98 Liebert Corporation

15

Rev. (08-JULY-98)

LGM Module Driver

Parameter Page

Function Block Type: LGM (LGM Module Driver)

Name SiteGate-232 Line 1 LG 2 CM 1 FB 15 Flags —

ID ID14 Tele NB All Options Y Type 67 Ver 1

Power Up Delay 0 (sec) Demand Controller Address 0 ,0

Update Time 0:00 (mm:ss)

BACnet Device Parameters:

Use default device object name? Y Device Name =

Use default device object ID? Y Device ID = (device object, 0)

APDU Timeout ............. 3000 (milliseconds)

Number of APDU Retries ... 0

GFB performance tuning:

=======================

Time slice per GFB = 5000 milliseconds.

CMnet Parameters:

General:

Generate a “Dead Module” alarm after 10 minutes of no communications

with a control module.

Zero compression enabled? YES

Output character pacing? (reduces throughput by 50%) NO

Delay before sending all replies (20 msec minimum) = 20 msec.

Interpacket delay .............. (20 msec minimum) = 20 msec.

Alternate interpacket delay .... (40 msec minimum) = 40 msec.

CMnet Tuning Parameters: (Tech Support Only)

Time to wait for ‘?’ before attempting intrusive grab = 500 msec.

Maximum number of intrusive grab attempts per request = 3

Grab Silence Time = 600 msec.

Time to hold the token when the token wraps around = 1 seconds

Time to wait for each module to acknowledge the token = 500 msec.

Maximum online time per successful grab = 0:50 (mm:ss)

Maximum monitor time per monitor request = 5:00 (mm:ss)

Console Port #1 Parameters:

Modem installed on this console port = NO

Modem control parameters:

Modem Reset ATV0E0Q0S0=1S7=60

Dial Prefix ATDT

Phone Number

Use This Number? NO (NO = use number from SETGCM )

If not connected, and with no alarms pending delivery, reset modem

every 5:00 (mm:ss). Note: the minimum value for this is 5:00.

If connected, but no activity has been detected for 20:00 (mm:ss),

hang up and reset modem.

After dialing, wait 2:00 (mm:ss) for connection before hanging up.

After unsuccessful alarm delivery, wait 5:00 (mm:ss) before

trying again.

Escape (+++) guard time 1000 msec.

Post hangup delay 1000 msec.

Reset time (DTR low) 1000 msec.

Post DTR high delay 500 msec.

Post reset string delay 1000 msec.

Console Port #2 Parameters:

Modem installed on this console port = NO

Modem control parameters:

Modem Reset ATV0E0Q0S0=1S7=60

Dial Prefix ATDT

Phone Number

Use This Number? NO (NO = use number from SETGCM )

Advertising