20

3

General

venting

Installation & Operation Manual

5. Dry

fi t vent or air piping to ensure proper fi t up before

assembling any joint. The pipe should go a third to

two-thirds into the fi tting to ensure proper sealing after

cement is applied.

6. Priming

and

Cementing:

a.

Handle

fi ttings and pipes carefully to prevent

contamination

of

surfaces.


b. Apply a liberal even coat of primer to the fi tting

socket and to the pipe end to approximately 1/2"

beyond the socket depth.


c. Apply a second primer coat to the fi tting

socket.


d. While primer is still wet, apply an even coat of

approved cement to the pipe equal to the depth of

the

fi tting socket along with an even coat of

approved cement to the fi tting socket.


e. Apply a second coat of cement to the pipe.


f.

While the cement is still wet, insert the pipe into

the

fi tting, if possible twist the pipe a 1/4 turn as

you

insert

it.

NOTE: If voids are present,

suffi cient cement was not applied and joint could
be

defective.


g. Wipe excess cement from the joint removing

ring or beads as it will needlessly soften the

pipe.

Table 3D PVC/CPVC Vent Pipe, and Fittings

Approved PVC/CPVC Vent Pipe and Fittings

Item

Material

Standard

Vent pipe

PVC Schedule 40, 80 ANSI/ASTM D1785

PVC - DWV

ANSI/ASTM D2665

CPVC Schedule 40, 80 ANSI/ASTM F441

Vent fi ttings

PVC Schedule 40

ANSI/ASTM D2466

PVC Schedule 80

ANSI/ASTM D2467

CPVC Schedule 80

ANSI/ASTM F439

Pipe Cement /

Primer

PVC

ANSI/ASTM D2564

CPVC

ANSI/ASTM F493

NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE

NOTE: In Canada, CPVC and PVC vent pipe, fi ttings and cement/
primer must be ULC-S636 certifi ed.

1. Work from the boiler to vent or air termination. Do not

exceed the lengths given in this manual for the air or vent

piping.
2. Cut pipe to the required lengths and deburr the inside

and outside of the pipe ends.

3. Chamfer outside of each pipe end to ensure even

cement distribution when joining.

4. Clean all pipe ends and fi ttings using a clean dry rag.

(Moisture will retard curing and dirt or grease will prevent

adhesion.)

6” COUPLING

(FIELD SUPPLIED)

6” CPVC

STARTER

PIECE

(FACTORY SUPPLIED)

VENT

THE 6” STAINLESS STEEL ADAPTER SUPPLIED
WITH THE BOILER MUST BE USED FOR VENT
CONNECTION TO PVC/CPVC. THE 6” CPVC
STARTER PIECE MUST BE USED FOR PVC ONLY.

Figure 3-3 Near Boiler PVC/CPVC Venting - Models
701 - 801

VENT

4" CPVC PIPE SUPPLIED WITH
BOILER MUST BE USED FOR VENT CONNECTION

NOTE:

CPVC VENT OR STAINLESS STEEL PIPE AND

VENT FITTINGS MUST BE USED IN CLOSET AND
ALCOVE INSTALLATIONS.

*

* 4” CPVC STREET ELBOW
MAY BE SUBSTITUTED

Figure 3-2 Near Boiler PVC/CPVC Venting - Models 400 - 601