Building Safety. Building Security.

Description

The Remote Tableau Drive Unit PTU288-1 allows to op-

tically signal events of a Fire Detection Control Panel

Series BC216 or BC016, or of an Extinguishing Control

Panel Series LC216, on an optional synoptic remote

tableau. In addition, a built-in buzzer signals the alarm

or fault condition of the control panel.

Up to 3 LED Display Fields LAB48 or LED Connection

Modules LAM48-1 can be connected to the remote tab-

leau drive unit in any combination.

In accordance to the parameterisation, the LEDs can be

used to display the conditions of detectors, detector zo-

nes, actuations, actuation elements, alarming devices,

transmitting devices, extinguishing systems or fl ooding

zones as well as the most important system conditions

of the fi re detection control panel (e.g., summary alarm,

fault condition or disablement condition). If needed, it is

also possible to combine several events into a summary

display.

Furthermore, the PTU288 has 5 freely parameterisable

control inputs.

The remote tableau drive unit is connected to the fi re

detection control panel via the INFO bus. Auxiliary mo-

dules are not needed for connection to Control Panels

Series BC216. A Serial Interface Module SIM016-3 is

necessary for connecting the PTU288 to a Fire Detec-

tion Control Panel Series BC016.

The PC software PARSOFT is used to parameterise the

remote tableau drive unit via the USB interface.

The componentry is prepared for direct installation into

the LED Display Tableau LAT288-1 or LAT288-1CE. The

componentry can also be mounted in any housing in the

LST standard grid, using the supplied mounting parts.

• Optically and acoustically signals

the events of a fi re detection or

extinguishing control panel

• Actuation of up to 144 LED pairs,

single LEDs or relays

• Single or summary indication

parameterisable

• Connection to the INFO bus
• Easy parameterisation by means of

PC software PARSOFT

Specifi cations

Operating voltage

15 – 31VDC

Current consumption at 24V

typ. 15mA (without LED modules)

Ambient temperature

-20°C to +60°C

Dimensions L × W × H

150 Ч 75 Ч 20 (mm)

Weight

76g

Order number

252012

Order name

Remote Tableau Drive Unit PTU288-1