Specifi cations

The addressable Intrinsically Safe Optical Smoke De-

tector AOEX-55000-640 (fi g. A) uses the scattered light

principle and was developed for the detection of smo-

ke particles in hazardous areas. The smoke detector

must always be connected via a safety barrier, which

has been approved for this detector, and a protocol

interface. Furthermore, the relevant country specifi c

regulations always have to be observed.

The proven ADM loop technology with Apollo/Discovery

protocol establishes a permanent communication be-

tween the fi re detection control panel and the detector.

That ensures a periodical function testing of the detec-

tor. In the control panel all types of fi res are detected by

continuously comparing fi re patterns.

Intelligent evaluation algorithms use the current condi-

tion of the sensing chamber to predict the likely time

of the next maintenance. Thus the alarm threshold is

automatically adjusted within the permissible range, de-

pending on the contamination. With that, the constant

response sensitivity of the detector is ensured for a

long time.

The two LEDs with 360° visibility indicate the activated

condition of the detector. The detector address is se-

lected by means of a code card in the detector base.

Therefore the detector can be changed without additi-

onal tools.

The detector is inserted into the IS Detector Base ASEX-

45681-215 (not illustrated) and it can be protected

against theft.

Ignition protection

intrinsically safe

Ex classifi cation

EEx ia IIC T5

Operating voltage

Supply through loop voltage

Current consumption

typ. 340µA (quiescent)

Ambient temperature

-20°C to +40°C (no condensation or icing)

Relative humidity

0 – 95% (no condensation)

Dimensions ш Ч H

100 × 42 (mm)

Colour

white

Weight

100g