PRODUCT DESCRIPTION

The DXS-72/EC is a photoelectric smoke alarm with a built-in
transmitter designed for use with Linear’s DXS and DX Format
receivers. When smoke is detected, the alarm sounds a loud local
alarm. Twenty seconds after the local alarm sounds, the built-in
transmitter sends a digitally coded wireless signal to its companion
receiver. The wireless signal will be repeated every 20 seconds as
long as smoke is still present.
The digital DXS code format features over a million possible codes.
The DXS transmitters are precoded at the factory to unique codes,
so no fi eld coding is required. The DXS-72/EC can send three
different codes: alarm, test and low battery status.
For versatility, any transmitter can be programmed into any receiver
channel.
Receivers must be programmed to the transmitter’s
code before system testing and operation.
Refer to the receiver’s
instructions for details on programming.
The unit is powered by two 9-volt alkaline or lithium batteries. These
batteries are supplied with the transmitter and can power the unit
for up to two years. Every hour, the DXS-72/EC will send a status
transmission to the receiver. The hourly signal updates the receiver
to the transmitter’s condition. By monitoring status transmissions, the
receiver can determine if a transmitter has a low battery or has been
removed from the system. If the battery voltage drops below a preset
level the alarm will sound low battery beeps and a low battery signal
will be sent to the receiver with status reports (some receivers can
report low battery status, others cannot).

NOTE: After replacing batteries, press transmitter test button

to reset “low battery circuit”.

REMOVE MOUNTING PLATE

DXS-72/EC FEATURES

INSTALL BATTERIES

CHOOSE ALARM LOCATION

INSTALL MOUNTING PLATE

PROGRAM RECEIVER

MOUNT ALARM ON PLATE

(760) 438-7000 • FAX (760) 438-7043

www.linearcorp.com

PRINTER’S INSTRUCTIONS:

INSTR,INSTL,DXS-72/EC, PHOTO SMOKE - LINEAR P/N: 220838 A - INK: BLACK - MATERIAL: 20 LB. MEAD BOND - SIZE: 8.500” X 11.000” - SCALE: 1-1 - SIDE 1 OF 2

MATCH UP
ALIGNMENT
TABS

TWIST SMOKE
ALARM CLOCKWISE
TO LOCK TO MOUNTING
PLATE

BATTERY
HOLDING
CUPS

TRANSMITTER
BOARD

TRANSMIT LED

TRANSMITTER
TEST BUTTON

PRESS TRANSMITTER TEST BUTTON
AFTER INSTALLING BATTERIES
TO RESET LOW BATTERY CIRCUIT

CONNECT AND
INSTALL TWO
9-VOLT BATTERIES

9-VOLT BATTERY TYPES:
EVEREADY 216, 522, OR 1222
DURACELL MN1604
GOLD PEAK 1604P, 1604S
ULTRALIFE LITHIUM U9VL

LIVING

ROOM

BASEMENT

HALL

BED

ROOM

BED

ROOM

Indicates required smoke alarm
Indicates optional smoke alarm
if door is not provided between
Living and Recreation Rooms

RECREATION ROOM

READ THE STANDARD FOR SMOKE ALARM
LOCATION ON THE BACK OF THESE INSTRUCTIONS

DETERMINE THE PROPER LOCATION FOR THE ALARM

PLASTIC
SINGLE-GANG
ELECTRICAL
BOX

SCREW
ANCHORS
FOR WALLBOARD

OR

PRESS TRANSMITTER
TEST BUTTON
TO SEND SIGNAL

REFER TO RECEIVER'S INSTRUCTIONS
TO PREPARE RECEIVER TO ACCEPT THE
TRANSMITTER'S CODE

MATCH UP
ALIGNMENT
TABS

TWIST SMOKE
ALARM CLOCKWISE
TO LOCK TO MOUNTING
PLATE

DXS

FORMAT