Hydronic piping

INDIRECT

DHW TANK

BACKFLOW

PREVENTER

PRESSURE

REDUCING VALVE

PRESSURE

GAUGE

ANTI-SCALD

MIXING VALVE

AIR SEPARATOR

EXPANSION

TANK

BALL VALVE

(TYPICAL)

DRAIN POINT

(TYPICAL)

MAKE UP WATER

ZONE CIRCULATORS

(TYPICAL)

FLOW CHECK

VALVE

(TYPICAL)

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

BOILER
CIRCULATOR

BOILER 2

(MEMBER 1)

DOMESTIC

HOT WATER

CIRCULATOR

UNION

(TYPICAL)

HOT

WATER

OUT

COLD

WATER

IN

BOILER 1

(LEADER)

SYSTEM SUPPLY

SENSOR

TEMPERATURE /

PRESSURE

GAUGE

DRAIN

MAY SUBSTITUTE

LOW LOSS HEADER

Y-STRAINER
(RECOMMENDED)
(TYPICAL)

ZONE #1

ZONE #2 ZONE #3 ZONE #4

Figure 6-5 Multiple Boilers - Single Temperature Zoned with Circulators

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

Model

Number of Units

2

3

4

5

6

7

8

Required Pipe Sizes

81

1-1/4" 1-1/2"

2"

2"

2-1/2" 2-1/2" 2-1/2"

106

1-1/2"

2"

2"

2-1/2" 2-1/2" 2-1/2"

3"

151

2"

2"

2-1/2" 2-1/2"

3"

3"

3-1/2"

211

2"

2-1/2"

3"

3"

3-1/2"

4"

4"

286

2-1/2" 2-1/2"

3"

3-1/2" 3-1/2"

4"

5"