Maintenance schedule – Lochinvar Knight Wall Mount Boiler 51 - 211 User Manual

Page 8

Advertising
background image

User’s Information Manual

2

Maintenance schedule

8

ƽ WARNING

Have leaks fixed at once by a qualified
service technician. Failure to comply could
result in severe personal injury, death, or
substantial property damage.

Operate relief valve

1. Before proceeding, verify that the relief valve outlet has

been piped to a safe place of discharge, avoiding any

possibility of scalding from hot water.

ƽ WARNING

To avoid water damage or scalding due
to valve operation, a metal discharge
line must be connected to the relief
valve outlet and run to a safe place of
disposal. This discharge line must be
installed by a qualified heating installer or
service technician in accordance with the
instructions in the Knight Wall Mount
Installation and Operation Manual. The
discharge line must be terminated so as
to eliminate possibility of severe burns
or property damage should the valve
discharge.

2. Read the boiler pressure/temperature gauge to make

sure the system is pressurized. Lift the relief valve

top lever slightly, allowing water to relieve through

the valve and discharge piping.

3. If water flows freely, release the lever and allow the valve

to seat. Watch the end of the relief valve discharge pipe

to ensure that the valve does not weep after the line has

had time to drain. If the valve weeps, lift the seat again to

attempt to clean the valve seat. If the valve continues to

weep afterwards, contact your qualified service

technician to inspect the valve and system.

4. If water does not flow from the valve when you lift the

lever completely, the valve or discharge line may be

blocked. Immediately shut down the boiler, following

the operating instructions on page 9 of this

manual. Call your qualified service technician to inspect

the boiler and system.

Shut boiler down (unless boiler is used

for Domestic Water)

1. Follow “To Turn Off Gas to Appliance” on page 9 of this
manual.

2. Do not drain the system unless exposure to freezing

temperatures will occur.

3. Do not drain the system if it is filled with an antifreeze
solution.

4. DO NOT shut down boilers used for domestic water

heating, they must operate year-round.

3. Replace the front access door.

Test low water cutoff (if installed)

1. If the system is equipped with a low water cutoff, test the

low water cutoff periodically during the heating season,

following the low water cutoff manufacturer’s
instructions.

Reset button (low water cutoff)

1. Testing the low water cutoff shuts the unit off. Press the

RESET button on the low water cutoff to turn the unit

back

on.

Check boiler piping (gas and water)

1. Remove the boiler front access door and perform a gas

leak inspection per steps 1 through 7 of the Operating

Instructions on page 9. If gas odor or leak is

detected, immediately shut down the boiler following the

procedures on page 9. Call a qualified service

technician.

2. Visually inspect for leaks around water piping.

Also inspect the circulators, relief valve, and fittings.

Immediately call a qualified service technician to repair

any

leaks.

Figure 2-3 Air Vent

MANUAL

AIR VENT VALVE

Check air vents

1. Reference

FIG.

2-3

below.

2. Visually inspect vent to make sure that no leaks are

present.

3. If there is leaking, tighten the pin valve.

4. If the leaking continues, replace the air vent.

Advertising