Electrical specifications, Refrigerant line specifications – LG LA090HP User Manual

Page 31

Advertising
background image

28

Floor Standing

Ceiling Cassette

Type

A/C

A/C

A/C

A/C

System #

LF300CP

LF480CE

LC240CP

LC340CP

Indoor

230/208

230/208

230/208

230/208

BTUs

28,000

48,000

24,000

34,000

Rated

Amps

11.5/11.5

20.0/20.0

11.5/12.4

15.1/16.5

MCA*

17***

28.9***

17.3

27.5

MOP**

25***

50***

30

50

Electrical Specifications

Outdoor

230/208

230/208

230/208

230/208

Voltage

All equipment single phase.

NOTE: Please see local electrical codes for proper wire specifications.

*Minimum Circuit Ampacity

**Maximum Overcurrent Protection

***Floor standing MCA + MOP calculated for indoor and outdoor

units connected to common breaker (Preferred method).

Wire Size

Minimum AWG

14-3

Indoor/Outdoor Connecting Cable Minimum AWG

14-3

Floor Standing

Ceiling Cassette

Type

A/C

A/C

A/C

A/C

System #

LF300CP

LF480CE

LC240CP

LC340CP

Pipe size

Liquid Suction

3/8"

5/8"

3/8"

3/4"

1/4"

1/2"

1/4"

5/8"

BTUs

28,000

48,000

24,000

34,000

Additional
Refrigerant

0.32 oz./ft.

0.42 oz./ft.

0.32 oz./ft.

0.42 oz./ft.

Max. length
each pipe

100'

131'

100'

115'

Max.
elevation

66'

82'

50'

66'

Refrigerant Line Specifications

†Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.

NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement:
For systems with maximum elevation of 25 ft. (see Figure A), refrigerant lines must be oil trapped
between 8 ft. and 12 ft. of elevation.
For systems with elevation of greater than 25 ft. Refrigerant lines must be oil trapped at least
every 12 ft. of elevation.

* Each system should have a 6-8 inch inverted trap at the condensing unit if mounted above

indoor unit.

DUCT LESS

FLOOR STANDING & CEILING CASSETTE • SINGLE ZONE

ELECTRICAL & REFRIGERATION

QUICK REFERENCE

25' maximum

8' minimum
12' maximum

OIL TRAP

INDOOR UNIT

OUTDOOR UNIT

Figure A.
Example: 25 ft. maximum elevation.

Advertising