Operating information, C(operational information) – Lochinvar Wall Mount Boiler WH 55-399 User Manual

Page 72

Advertising
background image

72

Installation & Operation Manual

11

Operating information

Status Display Screens

(cont’d)

Section

Display

Description

C

(Operational

Information)

SYSTEM:

The temperature read by the system supply sensor (if connected).

TANK:

The temperature read by the tank sensor (if connected).

OUTDOOR:

The temperature read by the outdoor sensor (if connected).

INLET TEMP:

The temperature read at the inlet to the heat exchanger.

OUTLET TEMP:

The temperature read at the outlet of the heat exchanger.

DELTA T:

The temperature difference between the inlet and the outlet of the
heat exchanger.

FLUE TEMP:

The temperature read by the flue sensor.

FLAME CURRENT:

The current measured by the flame sense circuit.

FAN SPEED:

The speed of the combustion blower.

BOILER PUMP:

The status of the boiler pump output.

SYSTEM PUMP:

The status of the system pump output.

DHW PUMP:

The status of the DHW pump output.

BMS VOLTAGE:

The voltage received from a BMS system.

BLR PUMP OUTPUT:

The speed signal sent to a variable speed boiler pump in percent.

SYS PUMP INPUT:

The speed signal received from a variable speed system pump control.

RATE OUTPUT:

A 0 - 10V signal indicating the firing rate of the boiler.

SH RUN HOURS:

The total hours of operation in the Space Heating Mode.

SH CYCLES:

The total burner cycles in the Space Heating Mode.

DHW RUN HOURS:

The total hours of operation in the DHW Mode.

DHW CYCLES:

The total burner cycles in the DHW Mode.

LAST 10 FAULTS NO:*

The last 10 lockouts.

NIGHT SETBACK

Shows the next Night Setback trigger (if active).

Advertising