Wiring the boiler active inputs – Lochinvar Harmony User Manual

Page 6

Advertising
background image

6

• The System Prove feature is provided to check system component

operation.

• A typical use of this feature is to check for flow before firing any

boiler stages. When there is a call for heat, the System Output
activates the system pump starter. When the pump establishes flow,
a flow switch closes together the SYSTEM PROVE input. Only then
can the Harmony activate boilers and modulate them as required to
hold the temperature set point.

• If the SYSTEM PROVE input is open on a call, the Harmony will

enable only the System Output. All Stage outputs will be off when
the SYSTEM PROVE input is open.

• A factory installed jumper provides the System Prove signal. Do not

remove the jumper unless it will be replaced by a System Prove
signal.

• The System Prove signal must be a dry contact only. No voltage can

be placed across the SYSTEM PROVE - A9, A10 terminals.

• Bring the two wires from the dry contact to the terminals marked

SYSTEM PROVE - A9, A10.

IMPORTANT: Do not remove the factory installed System Prove

jumper unless it is replaced by a System Prove signal. If the
SYSTEM PROVE
input is not closed, the Harmony will NOT
activate stages.

WIRING THE BOILER ACTIVE INPUTS

• A closure across the BOILER ACTIVE terminals informs the Har-

mony that a boiler is running normally. If the BOILER ACTIVE
terminals open, the Harmony registers that the Stage has encoun-
tered a safety limit and can not be restarted without a manual reset.
The Harmony will not reactivate or modulate a Stage which is not
Active.

• The Boiler Active signal is not a safety, but use of these inputs will

significantly improve the Harmony's set point control performance in
the event of a Stage encountering a safety limit.

• A pair of BOILER ACTIVE terminals is provided for each stage.
• The Boiler Active signal must be a dry contact closure from the

boiler controlled by that Stage's output. For example, the Boiler
Active signal wired into terminals STAGE A (Terminals B1 and B2)
must come from the unit whose operating limits are connected to
terminals OPERATING LIMIT OUTPUTS A (Terminals 5 and 6).

• The BOILER ACTIVE terminals are dry contacts only. No voltage

can be placed across the them.

• Wire the Boiler Active signals to their respective STAGE terminals:

- STAGE A to Boiler Active Input terminals B1&B2
- STAGE B to Boiler Active Input terminals B3&B4
- STAGE C to Boiler Active Input terminals B5&B6
- STAGE D to Boiler Active Input terminals B7&B8

Dry Contact
System Prove
Signal

TEMP

SHUTDOWN

NETWORK

SYSTEM

PROVE

T

+

S

INPUTS

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

WARNING: The SYSTEM PROVE

input can not be used as a safety
limit. All equipment must have its
own certified limit and safety con-
trols as required by local codes.

STAGE

A

STAGE

B

STAGE

C

STAGE

D

Dry Contact
Active Signal

INPUTS

B1

B2

B3

B4

B5

B6

B7

B8

BOILER

ACTVE

WARNING: The BOILER ACTIVE IN-

PUTS can not be used as a safety
limits. All equipment must have its
own certified limit and safety con-
trols as required by local codes.

INSTINSTINSTINSTINST

ALLAALLAALLAALLAALLA

TIONTIONTIONTIONTION

INPUT WIRINGINPUT WIRINGINPUT WIRINGINPUT WIRINGINPUT WIRING

Advertising