LST SLR-E-IS User Manual

LST Safety

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

SLR-E-IS_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

• Conventional technology
• Optional connection of remote

indicator

• Extremely fl at design
• Function testable with test gas
• ATEX certifi ed

Specifi cations

Ignition protection

intrinsically safe

Ex classifi cation

EEx ia IIC T5

Current consumption at 24V

typ. 50µA (quiescent)

Ambient temperature

-10°C to +55°C

Relative humidity

10 – 95% (no condensation)

Dimensions ш Ч H (incl. base)

100 × 46 (mm)

Colour

cream

Weight

115g

Approval

BAS01ATEX1281

LPCB 164a

Order number

241090

Order name

IS Optical Smoke Detector/Conv. SLR-E-IS

The Intrinsically Safe Optical Smoke Detector SLR-E-IS

uses the scattered light principle and was developed

for the detection of smoke particles in explosion-prone

rooms.

The modern design of the sensing chamber al-

lows to reliably evaluate the characteristics of fi re.

Conventional technology is used for alarm transmission

to the fi re detection control panel. In conjunction with the

Safety Barrier ES58-2, the detector reaches the given

Ex classifi cation. The two LEDs with 360° visibility indi-

cate the activated condition of the detector. By means

of an auxiliary module, the connection to an ADM loop

is possible.

A detector function test can be conducted by using test

gas. The detector is attached to the IS Detector Base

YBN-R/4IS.

Advertising