Description

The Thermal Max Detector 4351E recognises a maxi-

mum temperature of 78°C as sign of fi re. It complies

with Class BS and can be used up to a room height

of 6m.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. The

detector addressing can be achieved in 2 ways:

• A detector with an Address Module NG58-1 can be

individually identifi ed by the suitable control panel.

• An address, which has been stored in the detector

by means of the Remote Programming and Test Unit,

is displayed on the Zonal Display Unit S300ZDU.

A test activation of the detector can be carried out

using the Remote Test Unit ECO1000RTU. In addition

to the test activation of the detector, the Remote Pro-

gramming and Test Unit S300RPTU can also be used

to set and display the following detector parameters:

• the detector address, and

• the date of the previous maintenance.

The detector can be attached to various detector ba-

ses and it can be protected against theft.

• Addressable conventional technology
• Alarm temperature 78°C
• Addressing by means of address

module or detector parameterisation

• Remote readout of detector condition
• Function testable with Remote Test

Unit ECO1000RTU

Specifi cations

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 85µA (quiescent)

Alarm temperature

78°C

Ambient temperature

-30°C to +70°C (continuous operation)

Relative humidity

5 – 95% (no condensation)

Dimensions ш Ч H

102 × 43 (mm)

Colour

cream

Weight

75g

Approval

VdS G202016

Order number

242041

Order name

Thermal Max Detector/Conv./300/SS 4351E