Pecifications – Liebert PSP User Manual

Page 26

Advertising
background image

22

S

PECIFICATIONS

Model Number

PSP500MT-230

PSP650MT-230

Power Rating VA/W

500VA/300W

650VA/390W

DIMENSIONS: mm (in.)

Unit
W x D x H

95 x 240 x 205

(3.7 x 9.5 x 8)

95 x 240 x 205

(3.7 x 9.5 x 8)

Shipping
W x D x H

171 x 332 x 293

(6.7 x 13.1 x 11.5)

171 x 332 x 293

(6.7 x 13.1 x 11.5)

WEIGHT: kg (lbs)

Unit

4.6 (10.2)

4.6 (10.2)

Shipping

5.7 (12.6)

5.7 (12.6)

INPUT AC PARAMETERS

Surge Protection

220J

Rated Input Voltage

230VAC

Voltage Range Without
Battery Operation

175VAC - 280VAC, DIP switch selectable

(see DIP switch settings on page 13)

Frequency Range

46.5 - 63.5 Hz (±0.1 Hz)

OUTPUT AC PARAMETERS

Output Receptacles

(4) IEC-320-C13 (orange)

Battery backup + surge protection

(2) IEC-320-C13 (black)

Surge protection

Voltage (Battery mode)

230VAC ±8%

Waveform (Battery mode)

Stepped Sinewave

Frequency

50 Hz or 60 Hz; auto sensing

Overload Warning
(Normal & Battery modes)

>100%

Overload Shutdown

>110%

BATTERY PARAMETERS

Type

Valve-regulated, nonspillable, lead acid

QuantityxVoltagexRating

1x12Vx7Ah

1x12Vx9Ah

Transfer Time

4 - 6 ms typical

Backup Time:

At 25°C (77°F), resistive loading, with fully charged batteries

Full Load

4 minutes

5 minutes

Half Load

17 minutes

14 minutes

Recharge Time

6 hours to 90% of rated capacity,

after full discharge into resistive load

ENVIRONMENTAL

Operating Temperature

0°C to +40°C

(+32°F to + 104°F)

Storage Temperature

-15°C to +40°C

(+5°F to +104°F)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3000m (10,000 ft.) at 30°C (86°F) without derating

Audible Noise

< 40 dBA, at 1 meter