FAULT

DESCRIPTION

CORRECTIVE ACTION

Temp O/Shoot

(continued)

(Lockout will reset
automatically after

5 minutes or may be reset

immediately once

condition has been

corrected. Press the

RESET button on the

SMART SYSTEM display

to reset.)

The temperature rise across the heat
exchanger has exceeded the set parameters
for the appliance.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the appliance is piped properly into the

heating system. Refer to Section 4 - Water
Connections

of the Power-fin Installation and

Operation Manual for the proper piping methods.

• Check for 120 VAC to the pump motor on a call

for heat. If voltage is not present, check the wiring
leading to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the

pump is not operating, replace the pump.

Outlet water temperature has exceeded the
maximum outlet water temperature.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the appliance is piped properly into the

system. Refer to Section 4 - Water Connections of
the Power-fin Installation and Operation Manual for
the proper piping methods.

• Check 120 VAC to the pump motor on a call for heat.

If voltage is not present, check wiring leading to the
main control board. Replace the main control board
if necessary.

• If 120 VAC is present on a call for heat and the pump

is not operating, replace pump.

• Replace the main control board.

Rem Ctrl Flt

External control is cycling too often.

• Check set point of the external control.

• Check the wiring between the external control and

the unit.

• Replace the control.

Parameters

Progr

(Will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM display

to reset.)

After downloading parameters from a laptop
or a pocket pc, the main control board must
be reset.

• Press the ENTER/RESET button on the Smart

System display panel.

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface