Maintenance – Lochinvar Hot Water Generator User Manual

Page 21

Advertising
background image

6

Maintenance

(continued)

Hot Water Generator Installation and Operation Manual

6.

Remove any sediment that is present in the strainers. If
they cannot be satisfactorily cleaned, replace with new
strainers.

7.

Place the strainers back on-line in the system.

8.

Reconnect the inlet and outlet lines to each strainer.
Follow recommendations contained in the
manufacturer’s documentation, local codes, or accepted
contractor practices as to the use and / or type of joint
compound or sealer at the connections.

9.

Follow the startup procedures (page 10) to put the unit
back on-line. Carefully check all connections for any sign
of leakage.

Traps - replacement (steam systems
only)

The main and auxiliary traps are installed upstream of the
condensate shutoff valve on units that use steam as the energy
source.

The traps are designed to maintain the flow of

condensate with the rise and fall of the float as changes in
condensate level occur within the body of the trap. If the
traps are not functioning properly and must be replaced,
follow the procedure outlined below.

ƽ

ƽ WARNING

The combination of electricity and water
can pose a very dangerous situation. Turn
off / disconnect all electric power before
attempting any maintenance procedure.

1.

Follow Steps 1 through 5 of the shutdown procedure
(page 10) to take the unit off-line before attempting to
replace the main or auxiliary traps.

2.

The exact location of the traps can differ depending on
the unit. Reference the CAD drawing supplied with the
unit to identify the location of the traps on the unit.

3.

Carefully break the joint on the inlet side of the trap.

4.

Carefully break the joint on the outlet side of the trap.

5.

Remove and examine the trap.

6.

If the trap is not functioning properly, replace it
with a new trap.

7.

Place the trap back on-line in the system.

8.

Reconnect the inlet and outlet lines to the trap. Follow
recommendations contained in the manufacturer’s
documentation, local codes, or accepted contractor
practices as to the use and / or type of joint compound or
sealer at the connections.

9.

Follow the startup procedure (page 10) to put the unit
back on-line. Carefully check all connections for any sign
of leakage.

21

Advertising