A

Building Safety. Building Security.

Description

• ADM loop technology with

System Sensor/200 protocol

• Can be activated with two different

tone types, 32 tone types selectable

• Sound level selectable in three steps

– up to 95dB(A)

• Low power consumption
• Versions with or without integrated

dual-isolator available

• Two base types available – IP24, IP44

Specifi cations

Operating voltage

Supply through loop voltage

Sound level (detector installed)

typ. 70dB(A) at 1m distance (low)

typ. 79dB(A) at 1m distance (medium)

typ. 87dB(A) at 1m distance (high)

max. 95dB(A) at 1m distance (high)

Ambient temperature

-25°C to +70°C

Dimensions ш Ч H

112 × 42 (mm) (without detector, incl. base LPBW)

Weight

134g

Colour

cream, RAL 9001

The loop powered sounder incorporates a detector

base and is fi tted into a round, white plastic case. It is

powered and actuated as a module through the ADM

loop with System Sensor/200 protocol. Fire Detectors

Series 200 can be fi tted into the integrated base.

The sounder can be activated by a Fire Detection Con-

trol Panel Series BC216 with two different tone types,

depending on the parameter setup. One of 32 different

tone type combinations can be selected with a DIL-

switch. The following tones are available, for example:

• Continuous tone 660Hz,

• Emergency signal according to DIN 33404,

• Slow whoop tone according to NEN 2575,

• Alternating tone 800/970Hz, and many more.

The sound level can be selected in 3 steps. The address

of the sounder is selected with two decadic rotary swit-

ches located at the bottom of the device.

The base sounder is designed for indoor surface moun-

ting. For this purpose a special base is needed. Two

different base types for protection classes IP24 or IP44

are available, depending on the application. An optional

mounting plate can be supplied for surface mounted

cabling.

The sounder is available in two different versions: With

or without integrated dual-isolator module.