Precisioncell ii m and msh, Guide specifications application guidelines, Hepa prefilters – Precisionaire PrecisionCell II M User Manual

Page 4: Component chart

Advertising
background image

1.0 General

1.1 Medium and high efficiency extended surface

filters shall be PrecisionCell II (M) (MHS) mini-
pleat panel filters as manufactured by Flanders
Precisionaire.

1.2 Filter sizes, efficiencies and capacities shall be

as scheduled on the drawings.

1.3 Filters shall be UL 900 Class 2 listed.

2.0 Filter Construction

2.1 The filter pack shall be constructed of water-laid

microfine fiberglass media containing a water
repellent binder formed into closely spaced pleats
held in position by adhesive bead separators.

2.3 The filter pack shall be enclosed and sealed with-

in a corrosion-resistant metal frame.

2.4 PrecisionCell II MSH filters shall have a single

13/16” diameter header on the air entering side.

3.0 Performance

3.1 Initial and final resistances shall not exceed t h e

scheduled values.

3.2 Media area must equal or exceed that of the

specified filter

3.3 The average efficiency shall be as determined

by ASHRAE Standard 52.1 and 52.2 test
methods.

3.4 The manufacturer shall guarantee performance

as stated in the literature within tolerances as
outlined in Section 7.4 of ARI Standard 850.

4

Guide Specifications

Application Guidelines

PrecisionCell II filters should be selected for
new installations with 24” H x 24” W and 24”
H x 12” W face sizes. These are the most
widely used and stocked sizes. This allows
for 12” increments in height and width of the
filter bank and insures that replacement car-
tridges will be readily available.

PrecisionCell II filters should be installed with
the pleats vertical wherever possible. It is
permissible to install 24” H x 12” W face size
filters with pleats horizontal if necessary to
meet the size requirements of the filter bank.

HEPA Prefilters

PrecisionCell II filters are ideal as prefilters
for Alpha Cell HEPA filters. Their light weight
and 4” depth make them an excellent choice
for installation in the optional Prefilter Frame Assembly for the Alpha Cell HEPA Filter Holding Frame or in
Surelock Side Access HEPA Housings.

Specify the Surelock housing with an optional 4” wide prefilter track for the PrecisionCell II filters, in lieu of
the 2” wide prefilter track for pleated panel filters. We recommend the selection of 80-85% PrecisionCell II
filters as HEPA prefilters.

PrecisionCell II M and MSH

Component Chart

88655. 04 20 24 MSH D

Efficiency Series
89655. - 90-95%
88655. - 80-85%
86655. - 60-65%
Nominal Depth
04 - 3.75” Deep
Nominal Width
20 - (19-3/8”) wide
Nominal Height
24 - (23-3/8”) tall

Frame Style
MSH - Metal
w-13/16”
Single Header

Gasket Location
D - Downstream
U - Upstream
V - One Vertical Side

REPRESENTED BY:

Flanders PrecisionAire

Foremost in Air Filtration

Toll Free 1-800-637-2803

Advertising
This manual is related to the following products: