Panasonic Fire Alarm Systems Heat Detectors 6275 User Manual

Page 2

Advertising
background image

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00012 2000-05-15

5

/

2006-08-31

Type numbers

6275

Heat detector, fixed temperature 60

°C, latching

6276

Heat detector, fixed temperature 80

°C, latching

Technical data

Voltage (V DC)

rated
allowed
normal

24
12-30
24

Current consumption at nom. volt.
(mA)

quiescent (detector only)
active (detector only)

Depending on the type of base it is plugged into. For more details, see
the base respectively.

0
Max. 70 (Current limitation in all EBL equipment)

Ambient temperature (

°C)

operating
storage

6275 / 6276

-10 to +40 / -10 to +60
-25 to +70 / -25 to +70

Ambient humidity (% RH)

max. 95, non condensing

Ingress Protection rating (estimated)

IP22

Alarm temp. (fixed temp.)

60

°C (6275), 80°C (6276)

Weight, detector only (g)

70

Colour

grey (N8, Munsell colour code)

Approvals

CE, EN54-5, response grade 1 (6275)

CE, EN54-8, temp. range 1 detector (6276)

Advertising
This manual is related to the following products: