Vent Termination Locations

The air inlet and exhaust outlet must be installed with the
following minimum clearances (see figure 6):

• Twelve inches above grade or maximum anticipated

snow level.

• Twelve inches from any opening through which flue

gases could enter the structure.

• Four feet horizontally and vertically from gas or electric

meters, gas regulators, dryer vents, vent hoods, bath-
room fan exhaust, attic fans and turbines.

• Two feet from an inside corner formed by two exterior

walls.

• Two feet from porches, decks, overhangs and other

obstructions.

In addition to maintaining the minimum clearances , the
vent should terminate according to the following guidelines:

1. Use only 2 inch pipe or a 2 inch concentric vent on

the vent termination for 100,000 - 150,000 BTU/Hr
models. For inputs of 175,000 BTU/Hr or more, use
only 3 inch pipe or a 3 inch concentric vent. Do not
expose any 3” X 2” reducers or bushings to out-
door ambient temperatures.

2. The air inlet and exhaust outlet must not terminate

under a patio, deck or any covered area.

3. Do not terminate the vent near walkways or into alleys

or other publicly accessible areas.

4. Do not terminate the vent in an area where children

or animals could block pipes.

5. Do not locate the vent terminal too close to shrubs or

bushes.

6. Caulk all cracks, seams and joints within 6 feet horizon-

tally above and below the vent.

7. Combustion air inlet termination and exhaust air termi-

nation must be located in the same pressure zone.

Figure 6: Minimum Clearances for Inlet/Outlet and Concentric Vent

A. 12 in (30 cm) min. clearance above grade,

veranda, porch, deck, balcony, or maximum

anticipated snow level.

B. 12 in (30 cm) min. clearance on top and side of

window or door that may be opened. Do not install

below a window or door that may be opened.

C. Clearance to permanently closed window.**
D. 12 in (30 cm) min vertical clearance to ventilated

soffit located above the terminal within a horizontal

distance of 2 ft (61 cm) from the center line of the

terminal.

E. 12 in (30 cm) min. clearance to unventilated soffit.
F. Clearance to outside corner **
G. 2 ft (61 cm) clearance to inside corner formed by

two exterior walls.

H. 4 ft (122 cm) clearance to each side of center line

extending above meter/regulator assembly.

I.

4 ft (122 cm) clearance to service regulator vent

outlet.

J. 12 in (30 cm) clearance to nonmechanical air

supply inlet to building or the combustion air inlet

to any other appliance.

K. 3 ft (91 cm) above if within 10 ft (3 m) horizontally of

mechanical air supply inlet.

**Clearance in accordance with local installation codes and the requirements of the gas supplier.

A. 12 in (30 cm) min. clearance above grade,

veranda, porch, deck, balcony, or maximum

anticipated snow level.

B. 12 in (30 cm) min. clearance on top and side of

window or door that may be opened. Do not install

below a window or door that may be opened.

C. Clearance to permanently closed window.**
D. 12 in (30 cm) min vertical clearance to ventilated

soffit located above the terminal within a horizontal

distance of 2 ft (61 cm) from the center line of the

terminal.
E. 12 in (30 cm) min. clearance to unventilated soffit.
F. Clearance to outside corner. **
G. 2 ft (61 cm) clearance to inside corner formed by

two exterior walls.

H. 3 ft (91 cm) within a height 15 ft (4.57 m) above the

meter/regulator

assembly.

I. 4 ft (122 cm) clearance to service regulator vent outlet.
J. 12 in (30 cm) clearance to nonmechanical air

supply inlet to building or the combustion air inlet to

any other appliance.

K. 6 ft (1.83 m) clearance to mechanical air supply inlet.

US Installations

Canadian Installations