Chiller p/t controller wiring schematic – Parker Hannifin R-22 User Manual

Page 4

Advertising
background image

Evaporator

DI1

1- = Black

1S = Green

1+ = Red

R = Red

G = Green

W = White

B = Black

TS2 - Temp. Sensor 2

TS1 - Temp. Sensor 1

PB1 PB2

8.8.

Temperature

Sensor

SEI/SEH

TS2

TS1

B

W

G

R

1+ 1S

1-

DI1

24

V

AC

24 VAC

40 VA

Transformer

Pumpdown

Relay

(optional)

Pressure

Transducer

Valve 2 connections

on left block when used

SD-252-408

Pressing the UP button will increase the set point by 1 unit.

Pressing the DOWN button will decrease the set point by 1 unit.

Pressing the ENTER button will change the flashing digit from 1’s digit

to the 100’s digit.
Press and hold the UP button and ENTER button together for 5 seconds to

save the set point. The digits will stop blinking.

CHANGING

REFRIGERANTS

Press and hold the UP button and ENTER button simultaneously for 5

seconds to enable the controller to change to another type of refrigerant.

All 4 digits will start to blink.
Pressing the UP button or the DOWN button will change the display to

other refrigerants.
When the display shows the desired refrigerant, press and hold the UP

button and ENTER button for together 5 seconds. The controller will save

and use the selected refrigerant’s table for saturated temperature. The digits

will stop blinking.

CHANGING VALVE TYPES – LGE1, SML1, or MED1

Press and hold the UP button and ENTER button for 5 seconds to enable

the controller to change to the other type of valves. All 4 digits will start

to blink.
Pressing either the UP button or the DOWN button will change the dis-

play between the different valve types. Press and hold the UP button and

ENTER

button together for 5 seconds to save the selection. The digits

will stop blinking.
Pressing the UP button and the DOWN button simultaneously will toggle

the display between AC circuit 1 and AC circuit 2.

AC CIRCUIT 2 MENU

The preceding instructions apply to AC circuit 2 as well as AC circuit 1:
SUP2

Superheat read by controller for AC circuit 2

POS2

Number of steps valve is open (0-6386) for AC circuit 2

PRS2

Pressure read by the transducer (0-153 PSI, gauge) for AC

circuit 2

TMP2

Temperature read by the temperature sensor (-50 to 103°F) for

AC circuit 2

TST2

Saturated temperature for AC circuit 2

AC2, PDN2

AC2 when in normal operation, PDN2 when in pumpdown for

AC circuit 2

R22, 134A, 407C, 404A, R507

R22 for refrigerant R-22, 134A for refrigerant R-134a, 407C for

refrigerant R-407C, and 404A for refrigerant R-404A and R507

for refrigerant R-507. Note: Not all controllers have both

R-507 and R-407C.

LGE2, SML2, MED2, ESX2

LGE2 if the EEV used is an SEI-50 or larger for AC circuit 2.

SML2 if the EEV used is smaller than an SEI-25 for AC circuit 2.

MED2 if the EEV used is a SEI-25 for AC circuit 2.

ESX2 if the EEV used is a ESX for AC circuit 2.

SSP2

Superheat set point (0 to 16°F) for AC circuit 2. Default is

10°F.

MOP2

Maximum operating suction pressure set point (0 to 153 PSI)

for AC circuit 2. Default is 153 PSI.

CTS2

Cut out suction pressure set point for AC circuit 2 (0 to 153 PSI)

CLP2

Calibrate pressure transducer for AC circuit 2

CLT2

Calibrate temperature sensor for AC circuit 2

PRO2

Proportional gain set point for AC circuit 2. Number of steps

per degree that superheat is above or below the superheat set

point (5 to 255 steps per degree). Default is 45 for the LGE2

setting, 22 for the MED2 setting, or 11 for the SML2 setting.

INT2

Integral set point for AC circuit 2. Number of seconds the con-

troller waits to update the reference valve position. (1 to 120

seconds). Default is 10 seconds.

DER2

Derivative setpoint for valve 2. Advanced algorithm parameter

that determines the slope of the change control point. Default is

zero.

DON2

Time delay in seconds between end of pumpdown and com-

pressor start when Relay 1 is used to pilot the compressor con-

tactor. The pre-opens the valve before compressor start to avoid

nuisance low pressure safety trips. 2 seconds.

DOF2

Time in seconds that the valve is shut before the compressor

Relay 1 opens to stop the compressor. Allows refrigerant pump-

down/pumpout. Default is 2 seconds.

DST2

Used with DON2. Number of steps to pre-open the valve before

compressor start. Default varies with valve size.

Page 4

CHILLER P/T CONTROLLER WIRING SCHEMATIC*

© 2008 Sporlan Division, Parker Hannifin Corp., 206 Lange Drive, Washington, Missouri 63090

*Only valve 1 shown, valve 2 connected in similarly.

Advertising
This manual is related to the following products: