PVI Industries Tank Series User Manual

Maxim• packaged gas/oil water heater

Advertising
background image

MAXIM• PACKAGED GAS/OIL WATER HEATER

NICKELSHIELD

®

NICKEL-PLATED STORAGE TANK

250 GALLON TANK SERIES

MODEL NUMBER

40-2.8 N 250A-PGO

54-3.8 N 250A-PGO

72-5.0 N 250A-PGO

GPH Recovery at 40° to 120° F

500

670

900

GPH Recovery at 40° to 140° F

400

540

720

Input

Btu/h

400,000 540,000 720,000

Input, gph #2 Fuel Oil

2.8

3.8

5.0

A

Cold Inlet - NPT

2

2

2

B

Hot Outlet - NPT

2

2

2

C

Drain - NPT

1

1

1

D

I - Beam Skids

3 X 45

3 X 45

3 X 45

F

Overall

Height

75 82 82

G

Flue Outlet Diameter

7

8

10

H

Gas

Inlet

1 1 1

Minimum Inlet Flow Gas Pressure

4.5" W.C.

4.5" W.C.

6.5" W.C.

Maximum Static Gas Pressure

14" W.C.

14" W.C.

14" W.C.

J

Oil

Inlet

1/2 1/2 1/2

Motor HP 120 V, 1Ø, 60 Hz.

1/3

1/3

1/2

Motor

Amps

8

8

10

L

Height to Outlet

65

73

73

M

Height to Inlet

28

36

36

N

Overall

Depth

83 83 83

P

Depth of Burner Housing

31

31

31

Approx. Shipping Weight - lbs

1520

1600

1710

Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form # PV 6679

Product is patented in the U.S., Canada, and Mexico.

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

PV 6676 01/05

(800) 784-8326

• www.pvi.com

STANDARD ELECTRICAL REQUIREMENTS

VENTING REQUIREMENTS

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS

MOTOR VOLTAGE: 120V, 1Ø, 60 HZ.

SEE ABOVE CHART FOR BLOWER MOTOR AMPS

-.02" TO -.06" W.C. (NEGATIVE PRESSURE).

THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL

GAS CODE UNDER "FAN-ASSISTED".

1. Control Enclosure
2. ASME Temperature &
Pressure Relief Valve
3. 3” NPT Handhole
4. Door swing requires 18"
in front of the water heater

PVI RESERVES THE RIGHT TO CHANGE

THE DESIGN AND SPECIFICATION WITHOUT NOTICE

Advertising