Powerware 685 User Manual

Page 47

Advertising
background image

A---5

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

Installation Manual

164201408 Rev. P00 053002

Table C. External Wiring Requirements (UPS-to-Battery or Remote Disconnect-to-Battery)

NOTE: All specified wire sizes are 90_C rated copper minimum

UPS Cabinet

Battery Cabinet

UPS

Series/

Model

Torque

N-M

(lb-in)

Tool Size

Torque

N-M

(lb-in)

Tool Size

Wire

Size

UPS to

Battery

Integral

or

Separate

# of

Cabinets

Battery

Type

*

Battery

Cabinet

Series

160/125

685

H20

2

Integral

Supplied 3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/125

685

H20

2

Separate

300

kcmil

3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/125

1085

B27, B31,

B37, B47,

H30, H40,

H50

2, 3, or 4

Integral

Supplied 3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/125

1085

B27, B31,

B37, B47,

H30, H40,

H50

2, 3, or 4 Separate

300

kcmil

3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/150

685

H20

2

Integral

Supplied 3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/150

685

H20

2

Separate

300

kcmil

3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/150

1085

B27, B31,

B37, B47,

H30, H40,

H50

2, 3, or 4

Integral

Supplied 3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/150

1085

B27, B31,

B37, B47,

H30, H40,

H50

2, 3, or 4 Separate

300

kcmil

3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/160

685

H20

2

Integral

Supplied 3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/160

685

H20

2

Separate

300

kcmil

3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/160

1085

B27, B31,

B37, B47,

H30, H40,

H50

1, 2, 3,

or 4

Integral

Supplied 3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

160/160

1085

B27, B31,

B37, B47,

H30, H40,

H50

1, 2, 3,

or 4

Separate

350

kcmil

3/8I hex

42.4

(375)

3/8I hex

42.4

(375)

* BATTERY TYPE DESIGNATIONS: B = C&D, H = HAWKER

NOTE: The term “Separate” refers to battery cabinets that are not physically attached to the

UPS, are wired with external contractor supplied wiring, and use a single overcurent

protection and disconnect device located near the batteries.

The term “Integral” refers to battery cabinets that are physically attached to the UPS

and the wiring between them is internal. The power wiring is supplied with the

system, and they use the UPS battery switch as the battery isolation device.

The wire size rating for products up to and including the 160/160 are for the total

battery supply. Since these UPS units can only land one wire per DC connection

point, a common DC collector including an isolation device and overcurrent

protection should be used. Refer to applicable national or local code requirements

for your installation.