PVI Industries 1250N600A-TPO User Manual

Turbopower, Gas/oil, Packaged water heater

Advertising
background image

Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
"J" dimension is for the burner housing only. Gas train may exceed this dimension.
Standard gas train.

*

The information presented is for Natural gas 0.6 S.G.— For operation with propane (LP gas), consult factory.

Dimensions are in inches unless otherwise specified.

Higher inputs available. Consult the factory.

For standard and optional equipment, see form PV 6046.

Model

Number

Recovery gph

Input

Btu/h

Min. Inlet Flow

Gas Pressure

"W.C.

#2 Oil

gph

Dimensions (inches)

Blower

Motor

Shipping

Weight

lbs

40°- 120°F 40°- 140°F

A

B

C

J

HP

Volt/Ph/

Amps

750 N 600A-TPGO

750

600

600,000

4.5

4.3

46

6

1

31

1/2

115/1

∅/10

2720

1000 N 600A-TPGO

1000

800

800,000

6.0

5.7

46

8

1

31

1/2

115/1

∅/10

2760

1250 N 600A-TPGO

1250

1000

1,000,000

7.5

7.2

54

8

1

31

3/4

115/1

∅/14

2850

1500 N 600A-TPGO

1500

1200

1,200,000

7.5

8.6

54

8

1-1/4

31

1

115/1

∅/16

2930

2000 N 600A-TPGO

2000

1600

1,600,000

6.5

11.4

63

10

2

36

2

115/1/

∅24

3140

2500 N 600A-TPGO

2500

2000

2,000,000

8.0

14.3

65

10

2

36

2

115/1

∅/24

3260

TURBOPOWER

®

GAS/OIL

PACKAGED WATER HEATER

NICKELSHIELD

®

NICKEL-PLATED STORAGE TANK

TANK SERIES 600 GALLONS

PV 5460 03/04

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

(800) 784-8326

(817) 335-9531

www.pvi.com

Product is patented in the U.S., Canada, and Mexico.

STANDARD ELECTRICAL REQUIREMENTS

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL
REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN
OPTIONAL CONTROL CIRCUIT TRANSFORMER.

*

REAR ACCESS MODULE

MODEL PREFIX

M

L

STD or OPTIONAL

750-1500

23"

8"

OPTIONAL

2000-2500

23"

16"

STANDARD

*

GAS PRESSURE REQUIREMENTS

SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.

MAXIMUM STATIC INLET PRESSURE: 14" W.C.

FOR PRESSURES OTHER THAN LISTED, CONSULT FACTORY.

Pressure shown is for standard UL gas train. Additional controls

may increase pressure requirements.

VENTING REQUIREMENTS

-.02" TO -.06" W.C. (NEGATIVE PRESSURE)

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER SIZING, CONSULT

THE NATIONAL FUEL GAS CODE UNDER “FAN-ASSISTED.”

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN

AND SPECIFICATION WITHOUT NOTICE.

Advertising