RS232 Communications Protocol & Command Set

(continued)

Request Input Voltage Level
Transmit the input AC voltage status

Send to UPS:

?INPUTVOLTS<CR>

Response from UPS:

XXX<SP>VAC<SP>IN<CR>

XXX is the input AC voltage represented
in ASCII.

Request Output Voltage Status
Transmit the output voltage state

Send to UPS:

?OUTPUTSTAT

Response from UPS:

XXX<SP>VAC<SP>OUT<CR>

XXX is the output voltage represented
in ASCII.

If the UPS is not in AVR or BATTERY mode:
Response from UPS:

NORMAL<CR>

If the UPS is in AVR mode and boosting voltage by 13%
Response from UPS:

AVRBOOST1<CR>

If the UPS is in AVR mode and boosting voltage by 26%
Response from UPS:

AVRBOOST2<CR>

If the UPS is in AVR mode and bucking voltage by 11%
Response from UPS:

AVRBUCK1<CR>

If the UPS is in BATTERY mode
Response from UPS:

BATTERY<CR>

Request Load Level Status
Transmit the load level percentage.

Send to UPS:

?LOADSTAT<CR>

Response from UPS:

XX<SP>%LOAD<CR>

XX is the load percentage represented
in ASCII.

Request Battery Charge Level Status
Transmit the remaining battery charge percentage.

Send to UPS:

?BATTERYSTAT<CR>

Response from UPS:

XX<SP>%BATTERY<CR>

XX is the battery charge percentage
represented in ASCII.

Identify Equipment
Transmit the model number, firmware number and revision.

Send to UPS:

?ID<CR>

Response from UPS:

PANAMAX<CR>

M1500-UPS<CR>

FW<SP>PARTNUMBER<CR>

REV<SP>REVISION<CR>

List all Commands and Queries

Send to UPS:

HELP<CR>

Response from UPS:

MAIN_ON<CR>

MAIN_OFF<CR>

NCL_ON<CR>

NCL_OFF<CR>

BATTHRESH<CR>

BEEPON<CR>

BEEPOFF<CR>

RESTORE<CR>

?OUTLETSTAT<CR>

?INPUTVOLTS<CR>

?OUTPUTSTAT

?LOADSTAT<CR>

?BATTERYSTAT<CR>

?ID<CR>

HELP<CR>