A---45

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Table P. UPM Output-to-SSBM Cable and Conduit Configurations: For Max Number of UPMs

UPM Output-to-SSBM Cable Configuration

Minimum Conductor Size, 3, (1) Neutral, (1) Gnd

Max No. of UPMs Connectable to each SSBM

(Based on UPM-to-SSBM Cable Configuration

9315

Model - kVA/kW

Output

Voltage

Output

Current

Conductor Size

(AWG or kcmil)

Number of

Conductors per

and Neutral

Number and

Size of Conduit

(in inches)

Model 2500

Model 3000

Model 4000

200 --- 200/160

400

290

500

1

1 --- 3.5

8

8

8

225 --- 225/180

208

625

500

2

2 --- 3.5

7

7

7

225 --- 225/180

480

271

400

1

1 --- 3.0

8

8

8

300 --- 225/180

480

271

400

1

1 --- 3.0

8

8

8

300 --- 225/180

600

217

300

1

1 --- 3.0

8

8

8

300 --- 300/240

208

830

400*

3

3 --- 3.0

4

4

4

300--- 300/240

480

360

4/0

2

2 --- 2.5

7

7

7

300--- 300/240

600

289

500

1

1 --- 3.5

8

8

8

250 --- 200/160

400

290

500

1

1 --- 3.5

8

8

8

250 --- 250/200

400

360

4/0

2

2 --- 2.5

7

7

7

400 --- 300/240

400

433

300

2

2 --- 3.0

7

7

7

400 --- 400/320

400

577

500

2

2 --- 3.5

7

7

7

500 --- 400/320

208

1110

500*

4

4 --- 3.5

3

3

3

500 --- 400/320

480

480

350

2

2 --- 3.0

7

7

7

500 --- 500/400

480

600

500

2

2 --- 3.5

7

7

7

500 --- 500/400

600

480

350

2

2 --- 3.0

7

7

7

625

500/400

400

722

350

3

3 --- 3.0

4

4

4

625 --- 500/400

400

722

700

2

2 --- 4.0

7

7

7

625

500/450

400

722

350

3

3 --- 3.0

4

4

4

625 --- 500/450

400

722

700

2

2 --- 4.0

7

7

7

625 --- 625/500

400

902

500

3

3 --- 3.5

4

4

4

625 --- 626/562

400

902

500

3

3 --- 3.5

4

4

4

750

625/500

480

752

350

3

3 --- 3.0

4

4

4

750 --- 625/500

480

752

700

2

2 --- 4.0

7

7

7

750 --- 625/500

600

601

500

2

2 --- 3.5

7

7

7

750

625/562

480

752

350

3

3 --- 3.0

4

4

4

750 --- 625/562

480

752

700

2

2 --- 4.0

7

7

7

750 --- 625/562

600

601

500

2

2 --- 3.5

7

7

7

750 --- 750/600

480

902

500

3

3 --- 3.5

4

4

4

750

750/600

600

722

350

3

3 --- 3.0

4

4

4

750 --- 750/600

600

722

700

2

2 --- 4.0

7

7

7

750 --- 750/675

480

902

500

3

3 --- 3.5

4

4

4

750

750/675

600

722

350

3

3 --- 3.0

4

4

4

750 --- 750/675

600

722

700

2

2 --- 4.0

7

7

7

DESCRIPTION:

DRAWING NO:

SHEET:

164201373---14

UPM OUTPUT-TO-SSBM CABLE AND

2 of 2

CONDUIT CONFIGURATIONS

NOTES:

1. The cable configurations shown support connection of the maximum number of UPMs for each SSBM model. The maximum number

of UPMs connected to any SSBM shall not exceed eight.

2. Maximum conductor size considered: 700 kcmil.

3. * = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements

between the UPS and its output transformer.