0 maintenance – Patterson-Kelley DVSCM-02 User Manual

Page 12

Advertising
background image

Thermific

®

Gas-Fired Boiler

Operation/Maintenance

Page 10

When the chart is completed, set up your boiler's
combustion to the corresponding information at the
temperature relative during the time of the start up.

Enter your 100º F

operational range.

% Oxygen

% Carbon

Dioxide

8

7.2

7.9

7.3

7.8

7.4

7.7

7.4

7.6

7.5

7.5

7.5

7.4

7.6

7.3

7.6

7.2

7.7

7.1

7.7

7.0

7.8

6.9

7.8

6.8

7.9

6.7

8

6.6

8

6.5

8.1

6.4

8.1

6.3

8.2

6.2

8.2

6.1

8.3

6

8.3

Important: measure combustion air temperature at the
unit; do not assume the combustion air temperature is
the same as the outside air temperature.

4.2.1 Combustion Air Requirement, SCFM

Series

700

Series

1000

Series

1200

Series

1500

Series

1700

Series

2000

170

251

291

364

413

501

5.0 MAINTENANCE

Maintenance procedures for the Direct Vent option are
the same as for the standard Thermific® model. Refer
to the Thermific Installation and Owner's Manual.
"TBIG," latest edition.