Application Guidelines

Precision Pak XDH filters should be selected using
24” x 12” and 24” x 24” face sizes. This allows for 12”
increments in height and width of the filter bank and
insures that replacement filters will be readily avail-
able.

Precision Pak XDH filters should be installed with
pockets vertical wherever possible. It is acceptable to
install 24” x 12” face size filters with pockets horizon-
tal if necessary to meet the size requirements of the
filter banks.

VAV Systems

VAV systems can be designed using the full range
depth of Precision Pak XDH filters. Filter banks
should be sized so that the maximum rated flow at
design conditions falls within the published recom-
mended velocities. Precision Pak XDH filters in all
standard depths can be applied at any capacity
between zero flow and catalog-rated capacities.

Installation Considerations

Precision Pak XDH bag filters may be installed in
Flanders Astr Holding Frames, K-Trac Filter Framing
Modules, Sureseal Side Access Housing or in similar
existing hardware.

Astr Holding Frames are riveted together to form a
bank and may be installed for upstream or down-
stream service. K-Trac Filter Framing Modules are
especially suitable for medium to large built-up filter
banks. Smaller systems and systems with minimum
upstream access space are best served using
Sureseal Side Access Housings.

Gasketed Headers

Precision Pak XDH filters installed in Flanders K-Trac
Filter Framing Modules or Sureseal Side Access
Housings require polyfoam gaskets on opposite head-
er sides to prevent air bypass.

To specify Precision Pak XDH filters with gasketed
headers, add suffix “S” or “H” to the model number.
Use “S” gaskets on the sides parallel to the pockets
and “H” for gaskets on sides perpendicular to the
pockets.

Prefilters

Properly selected bag filters without prefilters will gen-
erally require changeout annually in typical HVAC
applications. Because of the frequent maintenance
expense and increase in fan kW input using prefilters,
they are seldom recommended on lower efficiency
final filters.

1.0 General

1.1 Medium and high efficiency self-supporting fil-

ters shall be Precision Pak XDH extended sur-
face type as manufactured by Flanders.

1.2 Filter sizes, efficiencies and capacities shall be

as scheduled on the drawings.

2.0 Filter Construction

2.1 Filters shall be constructed of polyolefin micro-

fine synthetic media encased in a thin non-
woven polyester backer mat.

2.2 Open area on the filter face for air passage shall

be not less than 90%.

2.3 Flexible internal support stitching shall maintain

individual pockets in a controlled form under all
rated air flow conditions.

Stitching shall be

sealed with thermoplastic resin. Edges shall be
finished with a four-thread overlock stitch to pre-
vent air bypass.

2.4 Pockets shall be bonded to galvanized steel cas-

ings and assembled into a galvanized steel
header with reverse-hemmed edges for safety.

2.5 Headers shall be gasketed with polyfoam on

vertical sides to prevent leakage when installed
in framing modules or Side Access Housings.

2.6 Filters shall be UL 900 Class 2 listed.

3.0 Performance

3.1 Initial and final resistances shall not exceed the

scheduled values.

3.2 Media area must equal or exceed that of the

specified filter.

3.3 The average efficiency shall be as determined

by the ASHRAE Standard 52.1 and 52.2 test
methods.

3.4 The manufacturer shall guarantee performance

as stated in its literature within tolerances as
outlined is Section 7.4 of ARI Standard 850.

Guide Specifications

Flanders PrecisionAire

Foremost in Air Filtration

Toll Free: 1-800-637-2803