Panasonic 1826 User Manual

Page 2

Advertising
background image

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00277 2003-04-15

5

/

2008-08-18

Type numbers

1826

External Fire Brigade Panel. 1826SE / 1826CC: Designation texts on the front in
Swedish / see below. NOTE! In Swedish convention (SBF): No "General fault"
presentation.

1835

Printer for External Fire Brigade Panel 1826

1582

External FBP interface board. (Required in EBL512 / 500 when SW mode 1826/28 –
1582 2nd Cab
shall be used.)

1587

External FBP / DU interface board. (Required in EBL512 when SW mode 1826/28 –
1587
2nd Cab shall be used. EBL512 software V>2.3.2

1

required.)

2431

Connection board. (Required in EBL1000. SW mode 1826/28 – 1582 2nd Cab only.)

4552

RS485 Transceiver component / comm. module. (Required in EBL128. SW mode
1826/28 – 1587 2nd Cab only. EBL128 software V>1.0.5

1

required.)

1

Only required if the new function ("General fault" presentation) shall be used.

NOTE! The number of ext. FBPs that can be power supplied via the c.i.e. / board / external power
supply, is depending on if each 1826 unit has a printer or not, as well as all other units connected to the
same c.i.e. / board / external power supply.

2

Up to 1200 m cable can be used.

1826CC is a unit with a neutral front where the designation texts by production are made separately and
put into a transparent "text slot" for the LED and push button respectively. CC=Country Code.
The ext. FBP 1826 can run in one of two different SW modes:

a) 1826 in SW mode 1826/28 – 1587

2nd Cab

has the highest performance with regard to

functionality, response time, ability to store fire alarms, etc. and is intended to succeed the ext. FBP 2426
(1826+printer 1835 will succeed the ext. FBP 2425) but not as a spare part, since 1826, in this SW mode,
requires an Ext. FBP / DU interface board 1587 in the EBL512 c.i.e. and the look, dimensions, etc. are
not the same. This mode is always to be used when the ext. FBP is connected to EBL128.

b) 1826 in SW mode 1826/28 – 1582

2nd Cab

has the same functionality as the ext. FBP 2426 and can

be used as a spare part (1826+printer 1835 is a spare part for the ext. FBP 2425), i.e. the performance is
the same but the look, dimensions, etc. are not the same. 1826, in this SW mode, requires an Ext. FBP
interface board 1582 in the EBL512 / EBL500 c.i.e.

Technical data

Voltage (V DC)

rated
allowed

24
12-30

normal (in the system)
normal (in the system by battery back-up)

24
21-27

Current consumption at norm. volt. (mA)

Ext. FBP 1826
quiescent / active
Printer 1835
quiescent / active


26 (at 24 V), 48 (at 12 V) / 49 (at 24 V), 88 (at 12 V)

4 (at 24 V), 7 (at 12 V) / 161 (at 24 V), 345 (at 12 V)

Ambient temperature (

°C)

operating
storage

0 to +40
-40 to +70

Ambient humidity (% RH)

max. 90, non condensing

Ingress Protection rating (estimated)

IP52

Size W x H x D (mm)

415 x 290 x 128

Weight (g)

Ext. FBP 1826 (excl. printer)
Printer 1835 (incl. paper roll) / paper roll

5000
345 / 110

Colour (metal cabinet / door)

Light grey (NCS S 1500-N, PMS Cool grey 2) & aluminium sides.

Approvals

CE; Conforms with EN54-2 and –4 whenever applicable.
Conforms with SS3654 edition 1.

2

On each 1582 board are up to eight addresses available and on each 1587 board up to sixteen addresses. In EBL128

are up to four addresses available.