Guide specifications application guidelines, Gasketed headers, Prefilters – Precisionaire SwissAire Bag PB1104 User Manual

Page 4

Advertising
background image

Guide Specifications

Application Guidelines

SwissAire bag filters should be installed with pock-
ets vertical wherever possible. It is acceptable to
install 24” x 12” face size filters with pockets hor-
izontal if necessary to meet the size requirements
of the filter banks.

Gasketed Headers

SwissAire bag filters installed in Flanders K-Trac
Filter Framing Modules or Sureseal Side Access
Housings require polyfoam gaskets on opposite
header sides to prevent air bypass. To specify
SwissAire bag filters with gasketed headers, add
suffix ”SA” (side access), “GU” (upstream), “GD”
(downstream) and “GS” (sides) to model number.

Prefilters

Properly selected bag filters without prefilters will
generally require changeout annually in typical
HVAC applications. Because of the frequent
maintenance expense and increase in fan kW
input using prefilters, they are often recommended
with 90% efficient SwissAire final filters. However,
the energy cost to operate a prefilter seldom war-
rants their use with 50% or 60% filters.

1.0 General

1.1 Medium and high efficiency self-supporting filters

shall be SwissAire extended surface type as man-
ufactured by Flanders.

1.2 Filter sizes, efficiencies and capacities shall be

as scheduled on the drawings.

2.0 Filter Construction

2.1 Filters shall be constructed of 100% synthetic

media of sufficient rigidity to maintain self-support-
ing pockets.

2.2 Open area on the filter face for air passage shall

not be less than 90%.

2.3 Pockets shall be 100% welded, with no stitching to

provide protection against leaks and extra blow-out
strength.

2.4 Pockets shall be bonded to corrosion-resistant

steel casings and assembled into a corrosion-
resistant steel header.

2.5 Filters shall be UL 900 Class 1 rated.

3.0 Performance

3.1 Initial and final resistances shall not exceed the

scheduled values.

3.2 Media area must equal or exceed that of the spec-

ified filter.

3.3 The average efficiency shall be as determined

by the ASHRAE Standard 52.1 and 52.2 test
methods.

3.4 The manufacturer shall guarantee performance as

stated in its literature within tolerances as outlined
is Section 7.4 of ARI Standard 850.

Performance values shown in this publication may be averages or estimates intended to generally represent a product style.

Contact factory for latest actual test data on specific Flanders Precisionaire models

.

REPRESENTED BY:

Flanders - PrecisionAire

Foremost in Air Filtration

Toll Free: 1-800-347-2220

Advertising