4318 combination heat detector – Panasonic 4318 User Manual

Page 2

Advertising
background image

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00852 2007-01-11

3

/

2008-09-18

Type number

4318 Combination

heat

detector

Zone line

Ext. LED

End-of-line

device

C.i.e

. EBL5

12 / EBL128

/

EBL50

0

Zon

e

li

n

e

input

+

-

+

Mark

Mark

A+

B- L

B-

A+

A+

B- L

B-

A+

In the detector:

See also "Engineering Instructions for detectors Type 435x".

A

Contact for base 2324

B

Contact for base 2324

The detector is plugged in a base 2324. End-of-line device depending on the zone line input.

Technical data

Voltage (V DC)

rated
allowed
normal

24
10-30
24

Current consumption at nom. volt.
(mA)

quiescent (detector only)
active (detector only)

Depending on the type of base it is plugged into. For more details see
the Product Leaflet respectively, e.g. MEW00008 (Base 2324).

0.015
min. 3

Ambient temperature (

°C)

operating
storage

-10 to +50
-25 to +70

Application temperature class A1 (

°C)

typical / max.

+25 / +50

Ambient humidity (% RH)

max. 95, non condensing

Ingress Protection rating (estimated)

IP51

Alarm temp. (T=

°C; deltaT=

°

C/168s)

59; 18 (T=static response temp. Class A1 T

min.

=54; T

max.

=65.)

Size

∅ x h (mm)

102 x 39

Weight (g)

54

Construction / Colour

Modified polycarbonate / Grey (N8, Muncell colour code)

Approvals

07 EC Certificate no. 0845-CPD-232.1566; EN54-5, class A1R.

A

B

The zone line is connected to the base 2324 (A+ & B-)
Ext. LED is connected to the base 2324 (A+ & L).