Burner setup & boiler operation – PB Heat EC Series User Manual

Page 18

Advertising
background image

16

BURNER SETUP & BOILER OPERATION

CARLIN BURNER SPECIFICATIONS

Boiler

Model No.

Firing Rate

Burner

Model No.

Air

Shutter

Nozzle Size

Pump

Pressure

Start-up Settings

Air Band

Head Bar

EC/ECT-03-075

.75

EZ-1HP

Blank

0.60 70° B DEL³

150 psig

0.55

0.60 - 0.65

EC/ECT-03-100

1.00

EZ-1HP

Blank

0.85 70° A DEL

150 psig

0.65

0.85 - 1.00

EC/ECT-03-120

1.20

EZ-1HP

Blank

1.00 70° A DEL³

150 psig

0.80

0.85 - 1.00

Boiler

Model No.

Burner

Model No.

Air

Shutter

Nozzle Size

Pump

Pressure

Start-up Settings

Head Dim. A

Air Band

EC/ECT-04-125

99FRD

Blank

1.00 x 70° B DEL³

150 psig

2

40% open

EC/ECT-04-150

99FRD

Blank

1.25 x 60° B DEL³

150 psig

3

60% open

EC/ECT-04-175

99FRD

Blank

1.50 x 60° B DEL

150 psig

4

100% open

EC/ECT-05-175

99FRD

Open

1.50 x 60° B HAGO³

150 psig

5

10% open

EC/ECT-05-200

99FRD

Open

1.65 x 60° B HAGO

150 psig

5

45% open

EC/ECT-05-250

99FRD

Open

2.00 x 60° B HAGO³

150 psig

8

100% open

EC/ECT-06-275

102CRD

Open

2.25 x 60° B DEL³

150 psig

6

100% open

EC/ECT-06-300

102CRD

Open

2.50 x 60° B DEL

150 psig

8

100% open

BECKETT BURNER SPECIFICATIONS (140 psig Pump Pressure)

Boiler

Model No.

Burner

Model No.

Burner Head

Static Plate

Nozzle Size

Start-up Settings

Head Setting

Air Shutter

Air Band

EC/ECT-03-075

AFG-L1¹

L1¹

3-3/8"

0.65 60° B HAGO³

9.0

2

N/A

EC/ECT-03-100

AFG-L1

L1

3-3/8"

0.85 60° B HAGO

10.0

1

N/A

EC/ECT-03-120

AFG-L1

L1

—²

1.00 60° B HAGO³

9.0

2

N/A

EC/ECT-04-125

AFG-F6

F6

2-3/4"

1.10 80° A DEL³

5.0

1

N/A

EC/ECT-04-150

AFG-F6

F6

2-3/4"

1.25 80° B HAGO

8.0

1

N/A

EC/ECT-04-175

AFG-F6

F6

2-3/4"

1.50 80° B HAGO³

10.0

3

N/A

EC/ECT-05-175

AFG-MV1

M-V1-3

1.50 60° B HAGO³

10.0

3

3

EC/ECT-05-200

AFG-MV1

M-V1-3

1.75 60° B HAGO

10.0

9

3

EC/ECT-05-250

AFG-MV1

M-V1-5

2.00 45° B HAGO³

10.0

5

5

EC/ECT-06-275

CF-375

L1-S

2.25 45° P HAGO³

10.0

6

2

EC/ECT-06-300

CF-375

L1-S

2.50 45° P HAGO

10.0

6

3

RIELLO BURNER SPECIFICATIONS

Boiler

Model No.

Firing Rate

Burner

Model No.

Nozzle Size

Pump Pressure

Start-Up Settings

Turbulator

Air Damper

EC/ECT-03-075

.75

F5

0.60 60° B DEL³

155 psig

0.5

2.1

EC/ECT-03-100

1.00

F5

0.85 60° W DEL³

145 psig

2.0

2.6

EC/ECT-03-120

1.20

F5

1.00 60° W DEL

145 psig

3.0

2.9

EC/ECT-04-125

1.25

F5

1.00 60° W DEL

155 psig

2.5

3.4

EC/ECT-04-150

1.50

F10

1.25 60° B DEL³

145 psig

1.5

3.1

EC/ECT-04-175

1.75

F10

1.35 60° B DEL

165 psig

2.0

2.5

EC/ECT-05-175

1.75

F10

1.35 60° B DEL³

165 psig

2.0

2.5

EC/ECT-05-200

2.00

F10

1.50 60° B DEL

170 psig

2.5

2.8

EC/ECT-05-250

2.50

F10

2.00 60° B DEL³

155 psig

3.5

4.2

EC/ECT-06-275

2.75

F10

2.25 60° B DEL³

150 psig

4.0

4.2

EC/ECT-06-300

3.00

F10

2.50 60°B DEL

145 psig

4.5

4.2

Table 5.1:

Carlin Burner Specifications

Table 5.2:

Beckett Burner Specifications

Table 5.3:

Riello Burner Specifications

Factory Installed Nozzles (Packaged Boilers or Burner Cartons) are indicated in Boldface.
1 Requires Low Firing Rate Baffle
2 Remove Static Plate for 1.20 GPH Rate
3 Shipped Loose with Packaged Boiler or Burner Carton

Advertising
This manual is related to the following products: