12. Specifications

MODEL

KIN

800AP

KIN

1000AP

KIN

1200AP

KIN

1500AP

KIN

2200AP

Capacity

800VA

1000VA

1200VA

1500VA

2200VA

Voltage

+/-25% at line input

INPUT

Frequency

50 or 60Hz +/-10% (auto sensing)

Voltage
(on battery)

Simulated sine wave at 100V/110/115V/120V/220V/230V/240V

+/-5%

Frequency
(on battery)

50 or 60Hz +/-0.5%

Voltage
Regulation
AVR

AVR automatically increase output voltage 15% above input

voltage if -9% to-25% of nominal. AVR decrease output voltage

13% below input voltage if+9% to +25% of nominal

Transfer time

2/4 milliseconds, including detection time

Spike Protection

320 Joules, 2ms

EMI/RFI filter

10dB at0.15MHz, 50dB at 30MHz

(for xxxAP models only)

Overload
Protection

UPS automatic shutdown if overload exceeds 110% of nominal at

60 second and 130% at 3 seconds.

Unit Input

Circuit breaker for overload & short circuit protection

10Base-T
Cable Port

Network (UTP, RJ-45)compatible jacks

OUTPUT

PROTECTION

And

FILTERING

Short Circuit

UPS output cut off immediately or input circuit breaker protection

Type

Sealed, maintenance-free lead acid batteries

With 3-6 years typical lifetime

Typical
Recharge Time

4 hours (to 90% of full capacity)

Protection

Automatic self-test & Discharge protection, Replace battery

indicator

BATTERY

Back up Time

10 - 30 minutes (depending on computer load)

Net Weight

Kg(lbs)

13

(28.6)

15

(33.0)

15.2

(33.4)

15.6

(34.3)

26.2

(57.6)

Shipping Weight
Kg(lbs)

14.2

(31.2)

16.2

(35.6)

16.4

(36.1)

16.8

(36.9)

28.2

(62)

Dimension(mm)
WxDxH

130 x 382 x 201

169 x 448 x 227

PHYSICAL

Input Inlet

IEC 320 power inlet

Battery
Back-Up

Slow beeping sound (about 0.47Hz)

Battery Low

Rapid beeping sound (about 1.824Hz)

ALARM

Overload

Continue beeping sound

INTERFACE

RS-232
Interface

Bi-directional communication port

Safety

Meet IEEE 587 standard

CONFORMANCE

Surge

cUL, TUV, CE, meet FCC

Ambient
operation

3,500 meters max. elevation, 0-95% humidity non-condensing

0-48 deg C

Audible noise

<48dBA (1 meter from surface)

ENVIRONMENT

Storage
condition

15000 meters max. elevation

© 1999 Powercom Co., Ltd. All right Reserved. All trademarks are property of their respective owners.
Specifications subject to change without notice.

14