Before you call for service, Normal operation, Abnormal operation – Panasonic CW-C83GU User Manual

Page 17

Advertising
background image

17

Before you call for service...

Before

you

call
for
service...

Troubleshooting Tips save time and money!
Review the chart below first and you may not need to call for service.

Problem

Possible Causes

What To Do

The air conditioner is
unplugged.

The fuse is blown/circuit
breaker is tripped.

Power failure.

Airflow is restricted.

The THERMOSTAT may
not be set high enough.

The air filter is dirty.

The room may have been
hot.

Cold air is escaping.

Cooling coils have iced up.

Ice blocks the air flow and
stops the air conditioner
from cooling the room.

• Make sure the air conditioner plug is pushed

completely into the outlet.

• Check the house fuse/circuit breaker box and

replace the fuse or reset the breaker.

• If power failure occurs, turn the mode control to OFF.

When power is restored, wait 3 minutes to restart the
air conditioner to prevent tripping of the compressor
overload.

• Make sure there are no curtains, blinds, or furniture

blocking the front of the air conditioner.

• Turn the knob to a higher number. The highest

setting provides maximum cooling.

• Clean the filter at least every 2 weeks.

See the operating instructions section.

• When the air conditioner is first turned on

you need to allow time for the room to cool down.

• Check for open furnace floor registers

and cold air returns.

• Set the air conditioner's vent to the closed position.

• See Air Conditioner Freezes Up below.

• Set the mode control at Med Fan or High Cool with

the thermostat at 1 or 2.

Air conditioner
does not start

Air conditioner
does not cool as it
should

Air conditioner
freezes up

Normal Operation

• You may hear a pinging noise caused by water being picked up and thrown against the condenser

on rainy days or when the humidity is high. This design feature helps remove moisture and improve
efficiency.

• You may hear the thermostat click when the compressor cycles on and off.

• Water will collect in the base pan during high humidity or on rainy days. The water may overflow

and drip from the outdoor side of the unit.

• The fan may run even when the compressor does not.

Abnormal Operation

Advertising