Powermate PM4025 User Manual

Pm4025, Standard features, 25kw 60hz

Advertising
background image

Page 1 of 4

(1)

Rated @ 30% Voltage Dip

(2)

Consult Factory for conformance to UL2200 on special models prior to ordering.

* Standby Power Rating Definition: All models rated on lp gas, derate 10% when using natural gas. Capable of supplying emergency power in lieu of utility power for the duration of the interruption.
There is no overload capacity available or specified for this rating. Single-phase units are rated at unity power factor. Three-phase units are rated at .8 power factor. Single-phase systems are dedicated single
phase (4-wire). Three-phase systems are 12-lead broad range reconnectable. When reconnecting a 12-lead alternator to single-phase, derate to 2/3 output. OTHER DERATION FACTORS: Engine power is
available to 77°F, barometric pressure of 29.5in. Hg & relative humidity of 60%. Altitude: Derate system performance 4% per 1000 feet above 500 feet. Temperature: Derate system performance 1% per 10°F
temperature increase above 77°F. Humidity: Derate system performance 1.5% per 10% relative humidity above 60%. For elevations above 8000 feet, consult factory.

Standard Features

Standard Features

Standard Features

Standard Features

Ford Industrial Engine

• Ford Model LRG425 4-Cylinder In-Line Engine
• Electronic, Distributorless Ignition Control Module
• Electronic Governing Provides 0.5% Frequency Control
• Engine Oil Drain Lines Provided
• Easily Accessible For Engine Service

Alternator

• 2/3 Pitch Winding For Reduced Harmonics
• Low Waveform Distortion
• Excellent Motor Starting
• Tropicallized Windings

Weather Enclosure

• 16 Gauge Steel Enclosure With Sound Material Installed
• Powder Painted Almond Color Finish
• Lockable (keyed alike) Doors With Sound Baffles
• Vertical Air Discharge For Optimal Sound Control
• Critical Grade Muffler Integral To Enclosure
• No Exterior Fasteners

Fuel System

• Operates On Liquefied Petroleum Gas Or Natural Gas
• Simple Field Conversion Between Fuels
• Integrated Governor- Throttle Body Assembly

Cooling System

• Rated To Operate In 104°F Ambient Temperatures
• Factory Filled With Environmentally Safe Propylene Glycol
• 500-Watt Thermostatically Controlled Circulation Heater Aids Starting

Main Line Circuit Breaker

• UL 489 Listed Breaker Is Included As Standard
• Conveniently Mounted Behind Lockable Door With Window

Digital Remote Start/Stop Controller

• Robust Control Package
• Highly Accurate Monitoring, Display & Protection
• Field Programmable To Custom Tailor For Users Needs
• Equipped With RS485 Output, Compatible With RDP110 Remote

Annunciator Panel

• Programable I/O’s- 2 Relay Output/3 Auxiliary Input Contacts
3-Year/1500 Hour Warranty

• Best Standard Warranty In Its’ Class

PM4025

Gaseous Fueled Stationary Standby

25kW

60Hz

All Specifications Subject to Change Without Notice

©2002 Coleman Powermate, Inc.

Coleman® is a registered trademark of the Coleman Company, Inc. used under license.

Propane Motor

MLCB

Model: PM4025

Standby Rating*

Full Load

Starting

Insulation

Rating

Voltage

Phase

Hertz

kW

kVA

Amps

SkVA

(1)

Class

Amps

120/240

1

60

25

25

104

43.5

H

110

120/208

3

60

25

31.5

86.7

53

H

100

120/240

3

60

25

31.5

75.2

66

H

90

277/480

3

60

25

31.5

37.5

66

H

45

Listed To The UL2200 Standard

(2)

Advertising