Table 5.4:

Pipe Capacity

Capacity of pipe of different diameters and lengths in cubic feet
per hour [cubic meter per hour] with a pressure drop of 0.3
inches of water (75 Pa) and specific gravity of 0.60. No
allowance for an ordinary number of fittings is required.

Table 5.1:

MI Boiler – Natural Gas

Table 5.2:

MI Boiler – LP Gas

Table 5.3:

MIH Boiler – Natural Gas

GAS PIPING

Model

Input

Cubic Feet / Hour

Cubic Meters / Hour

MI-03

70

2.0

MI-04

105

3.0

MI-05

140

4.0

MI-06

175

5.0

MI-07

195

5.5

MI-08

227.5

6.4

MI-09

260

7.4

Model

Input

Cubic Feet / Hour

Cubic Meters / Hour

MI-03

28

0.8

MI-04

42

1.2

MI-05

56

1.6

MI-06

70

2.0

MI-07

78

2.2

MI-08

91

2.6

MI-09

104

2.9

Pipe

Length in

Feet

[Meters]

3/4"

Pipe

1"

Pipe

1-1/4"

Pipe

1-1/2"

Pipe

10 [3.0]

278 [7.9] 520 [14.7] 1050 [29.7]

1600 [45.3]

20 [6.1]

190 [5.4]

350 [9.9]

730 [20.7]

1100 [31.1]

30 [9.1]

152 [4.3]

285 [8.1]

590 [16.7]

890 [25.2]

40 [12.2]

130 [3.7]

245 [6.9]

500 [14.2]

760 [21.5]

50 [15.2]

115 [3.3]

215 [6.1]

440 [12.5]

670 [19.0]

60 [18.3]

105 [3.0]

195 [5.5]

400 [11.3]

610 [17.3]

Maximum Capacity Correction Factors for
Specific Gravity other than 0.60.

Model

Input

Cubic Feet / Hour

Cubic Meters / Hour

MIH-03

65

1.8

MIH-04

97.5

2.8

MIH-05

130

3.7

MIH-06

162.5

4.6

Specific Gravity

0.50 0.55 0.60 0.65 0.70 0.75

Correction Factor

1.10

1.04

1.00

0.96

0.93

0.90

Specific Gravity

0.80 0.85 0.90 1.00 1.10 1.20

Correction Factor

0.87

0.84

0.82

0.78

0.74

0.71

Specific Gravity

1.30 1.40 1.50 1.60 1.70 1.80

Correction Factor

0.68

0.66

0.63

0.61

0.59

0.58