Nordyne Light Commercial Air Handler B5SM -090 User Manual

Page 6

Advertising
background image

6

• The B5SM-120 air handler has a dual circuit coil and

the B5SM-090 has a single circuit coil.

• The B5SM-120 air handler is charged through service

valves on the end of the liquid tube for each circuit.
These must be removed before brazing the line sets.
The B5SM-090 is charged through a service valve
inside the unit, which should not be removed.

Before brazing the B5SM-090, remove the core from

the service port. Failure to do this may result in a leak
at the service valve. Replace the core and cap once
brazing is complete.

• Optional equipment such as liquid line solenoid valves,

low ambient, etc., should be installed in strict accordance
with the manufacturer’s installation instructions.

Filter Requirements
B5SM air handlers are shipped with three permanent
1” fi lters; however the fi lter rack can be converted to
accommodate a 2” fi lter. To convert to a 2” fi lter:
1. Remove all fi lters from the unit.
2. Locate and remove the 4 screws (Figure 1) holding

the bottom fi lter slide assembly (latch end) to the fi lter
rack frame. NOTE: Be careful when removing the slide
assembly so it does not drop into unit and cause damage
to the coil.

3. Remove the 4 screws securing the “L” bracket to the

“Z” bracket.

4. Rotate the “L” bracket 180 degrees, and reposition it so

it mounts fl ush with the “Z” bracket. See Figure 1.

5. Secure the fi lter slide assembly together with the four

screws.

Table 2. Electrical Rating Data

MODEL

VOLTAGE

PHASE

Hz

FLA

HP

MCA

MOP

-090 & -120 J

208-230/460

3

60

6.6-6.6/3.3

2

8.3-8.3/4.2

15

-090 & -120 K

208-230

1

60

11.3-10.0

2

14.2-12.5

25-20

FLA = Full Load Amps, MCA = Minimum Circuit Ampacity, MOP = Maximum Over-Current Protection

Table 1. Pressure Drop Across Filters

Model

B5SM

Nominal

CFM

Filter

Size

Resistance

(W.C.)

090

2200

18 x 24 (1”)

0.03

2600

0.04

3000

0.05

3400

0.07

3800

0.08

4200

0.09

120

3000

18 x 24 (1”)

0.05

3400

0.07

3800

0.08

4200

0.09

4600

0.11

5000

0.13

6. Re-install the fi lter slide assembly back into the fi lter rack

frame and secure with the 4 screws removed earlier. If
replacing factory supplied fi lters with disposable fi lters,
use only 2” disposable fi lters.

Accessing the fi lters does not require tools and can be
performed from either side of the fi lter-rack. On the service
side of the unit, locate the release knob at the base of
the fi lter rack and rotate clockwise to unlock, then pull up
and out to remove the fi lter access panel. On the blower
side, use the same method but rotate counter-clockwise
to unlock.

Figure 1. Converting from 1” Filter to 2” Filter Applications

BRACKET CONFIGURATION FOR

2” FILTER APPLICATIONS

BRACKET CONFIGURATION

FOR 1” FILTER APPLICATIONS

(FACTORY SETTING)

“Z” BRACKET

“L” BRACKET

REMOVE 4 SCREWS FROM

FILTER RACK FRAME

FILTERS

FILTER BRACKET

LOCATION

REMOVE 4 SCREWS SECURING

“Z” BRACKET AND “L” BRACKET