Performance, Options, Engineering data – Lifebreath 195TRV User Manual

Page 2: Warranty

Advertising
background image

OPTIONS

99-104

Digital Electronic Timer - 20/40/60 min.

99-350

Lifestyles Ventilation Control
includes Programmable Time Clock and Dehumidistat

99-109

Air Sentry™ Air Quality Monitor designed to accept remotely
mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to accept
remotely mounted Control Pad.

99-160

Duct Heater w/ Electronic SCR Thermostat,
1 Kw, 7” (178 mm)

99-161

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 7” (178 mm)

99-186

Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6mm)
mesh screen

WARRANTY

Units carry a LIFETIME warranty on the heat recovery

core, a five year warranty on the ERV core and a 5 year replacement
parts warranty.

TRV Sales Sheet

Revised: 06/07

Total Recovery Ventilator

Model 195TRV/300TRV

49 "

(1245)

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19"

(483)

Ports

7" (178 mm)

CONDENSATE

DRAINS

BLOWERS

*NOTE:

Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.

MOTOR

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

DEFROST

DAMPER

DEFROST AIR

FROM INSIDE

Ports

6" (150 mm)

METAL CLASPS

HRV

Core

ERV

Core

ENGINEERING DATA

MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven
by a common PSC motor. 5 speed fan operation.
120 VAC, 1.5 Amps.

FILTERS - Washable air filters in exhaust and supply air streams.

MOUNTING THE TRV - Four threaded inserts at corners of case designed to
accept four reinforced polyester straps that are supplied with the unit.

DEFROST - Damper defrost system.

DEHUMIDISTAT - Adjustable Internal Dehumidistat.

CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.

CONTROLS - ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode,
Recirculation mode (on compatible units), (each mode has 5 speeds). Control
pad can be removed from HRV and remotely mounted.

WEIGHT 106 lbs. (48 kg) SHIPPING WEIGHT 108 lbs. (49 kg)

195DCS FANCURVE

225

175

200

100

75

125

150

50

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Air Flo

w (cfm)

Static Pressure (in H

2

0)

HIGH SPEED

*

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3
2
1

4

3

2

1

5

All units conform to CSA and UL standards.

DIMENSIONS 195TRV/300TRV

inches (mm

)

PERFORMANCE

Net supply airflow in cfm (L/s) against external static pressure

195TRV

300TRV

E.S.P

cfm

L/s

cfm

L/s

@ 0.1” (25 Pa)

203

(96)

265

(125)

@ 0.2” (50 Pa)

191

(90)

260

(123)

@ 0.3” (75 Pa)

182

(86)

250

(118)

@ 0.4” (100 Pa)

167

(79)

235

(111)

@ 0.5” (125 Pa)

155

(73)

220

(104)

VAC @ 60HZ

120

120

WATTS / Low speed

100

150

WATTS / High speed

173

333

Amp rating

1.5

2.9

300DCS FANCURVE

300

275

250

225

200

175

150

125

100

75

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Air Flo

w (cfm)

Static Pressure (inH

2

0)

HIGH SPEED

*

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3

2

1

4

3

2

1

5

*

Manufacturers Data

195TRV

300TRV

Advertising
This manual is related to the following products: