used on the loop (i.e. ionisation smoke, optical smoke, or heat
sensor)

5:DEVICE STATUS

The analogue value can be identified & the detector self-tested, the
detector LED and the Remote LED can be turned on either in the
enabled mode or the disabled mode.

6:LOOP CONTENTS

Panel reports loop content on the display.

7:ZONE ALLOCATION

255 zones (of which 64 are visible indication zones), programmable
across 8 loops and/or panel inputs.

8:ALARM TEST

Sounders operate for 1 second every 10 seconds.

9:DEVICE TEST

Illuminates the device LED. Pulses the fire LED on the panel and
sounds the internal buzzer. No sounder operation, System
automatically resets after 25 seconds ready for the next device test.

0:EXTENDED MENU

Provides access to extended menu as detailed below:

1:ALERT TRIP LEVELS

Analogue values 35 - 50 in increments of 5.

2:FIRE TRIP LEVELS

Analogue values 55 - 70 in increments of 5.

3:PANEL DELAY

Overridden by Delay Override, BGU or Evacuate.

Set enable period day/night, delay time 1-10 minutes
Enable/disable.

4:READ MEMORY

64 events - most recent first.

5:CLEAR PRINT QUEUE

Clears events in printer queue.

6:NUMBER OF DISPLAYS Sets number of panel displays/repeaters.
7:PRINT MEMORY

64 events - most recent first.

8:PRINT C/E DATA

Single output, loop address or full listing.


5.2.3 Access

level

3

8812

9:EDIT C/E DATA

Panel and loop (See Cause/effect programming guide).

0:NETWORK

Configures panels in a network.


5.3 Accessing

Engineer’s Menu


Note: You must operate the ACCESS CONTROLS keyswitch for all engineer’s and user
functions.

Step 1 - Press 4 ACCESS MENU to reveal the following:

0 9 : 0 4 : 2 6
P

a n e l

N

a

m

e

- - - - - - - - - - - - - - - - - - - -

E N T E R C O D E , P R E S S *


Step 2 - Press appropriate Engineer’s code as section 4.2 above

eg

7

2

1

8

*

to reveal the following:

S E L E C T L E V E L 2 O P T I O N
1 : S E T T I M E / D A T E

2: : I S O L A T E D E V I C E S

* N E X T P A G E # Q U I T

Step 3 - Press

*

to scroll through the Engineer’s Menu.


NOTE: No facility is accessible unless it is shown on-screen.