Chapter 3 connector information, I/o connector signal descriptions, Table 3-1. i/o connector signals – National Instruments DAQ M Series User Manual

Page 23: I/o connector signal descriptions -1, Connector information

Advertising
background image

© National Instruments Corporation

3-1

NI 6236 User Manual

3

Connector Information

The I/O Connector Signal Descriptions and

RTSI Connector Pinout

sections contain information about M Series connectors. Refer to
Appendix A,

NI 6236 Device Information

, for device I/O connector

pinouts.

I/O Connector Signal Descriptions

Table 3-1 describes the signals found on the I/O connectors. Not all signals
are available on all devices.

Table 3-1. I/O Connector Signals

Signal Name

Reference

Direction

Description

AI GND

Analog Input Ground—These terminals are the input bias
current return point. AI GND, AO GND, and D GND are
connected on the device.

Note: AI GND, AO GND, and D GND are isolated from earth
ground and chassis ground.

AI <0..3>±

AI GND

Input

Analog Input Channels 0 to 3±—For differential
measurements, AI 0+ and AI 0– are the positive and negative
inputs of differential analog input channel 0. Similarly, the
following signal pairs also form differential input channels:

<AI 1+, AI 1–>, <AI 2+, AI 2–>, <AI 3+, AI 3–>

Also refer to the

Analog Input Ground-Reference Settings

section of Chapter 4,

Analog Input

.

Note: AI <0..3>± are isolated from earth ground and chassis
ground.

AO <0..3>

AO GND

Output

Analog Output Channels 0 to 3—These terminals supply the
voltage output of AO channels 0 to 3.

Note: AO <0..3> are isolated from earth ground and chassis
ground.