Troubleshooting 7-17

On-screen error message

Cause

Action

0B71 System temperature out

of Range

Ambient temperature is out
of range.

Fan is faulty.

CPU/PCI module board is
faulty.

Check the setting in SETUP

Clean the fan.

Replace the fan.

Replace the CPU/PCI
module board.

0B80 BMC Memory Test Failed
0B81 BMC Firmware Code

Area CRC check failed

0B82 BMC core Hardware

failure

0B83 BMC IBF or OBF check

failed

BMC is faulty.

Replace the PCI module
board.

0B90 BMC Platform

Information Area
corrupted

0B91 BMC update firmware

corrupted

BMC is faulty.

0B92 Internal Use Area of

BMC FRU corrupted

SROM is faulty.

BMC is faulty.

Replace the PCI module
board.

0B93 BMC SDR Repository

empty

0B94 IPMB signal lines do not

respond

0B95 BMC FRU device failure
0B96 BMC SDR Repository

failure

0B97 BMC SEL device failure

BMC is faulty.

Replace the PCI module
board.

0B98 BMC SEL Overflow

SEL (System Event Log)
overflowed.

Erase the unnecessary SEL.

0BB0 SMBIOS - SROM data

read error

0BB1 SMBIOS - SROM data

checksum bad

SROM is faulty.

Back panel board is faulty.

Replace the back panel board.

0BD0 1st SMBus device

address not
acknowledged

0BD1 1st SMBus device Error

detected

0BD2 1st SMBus timeout
0BD3 2nd SMBus device

address not
acknowledged

0BD4 2nd SMBus device Error

detected

0BD5 2nd SMBus timeout
0BD6 3rd SMBus device

address not
acknowledged

Board is faulty.

Check cable connection.

Replace the board.