Taking measurements from two-wire rtds, Figure 6. two-wire rtd connections on one channel – National Instruments cFP-RTD-124 User Manual

Page 6

Advertising
background image

FP-RTD-124 and cFP-RTD-124

6

ni.com

negative terminals (COM and SENSE–). Connect the third wire to
the positive terminal (SENSE+). Use a short jumper wire to
connect the EXCITE+ terminal to the SENSE+ terminal.

Figure 5. Three-Wire RTD Connections on One Channel

Taking Measurements from Two-Wire RTDs

Connect one wire of a two-wire RTD to the SENSE+ terminal and
the other wire to the SENSE– terminal. Use a short jumper wire to
connect the SENSE+ terminal to the EXCITE+ terminal. Use
another short jumper wire to connect the SENSE– terminal to the
COM terminal.

Figure 6. Two-Wire RTD Connections on One Channel

SENSE+

[c]FP-RTD-124

SENSE–

COM

EXCITE+

Three-Wire

RTD

Short Jumper Wire

SENSE+

[c]FP-RTD-124

SENSE–

COM

EXCITE+

Two-Wire

RTD

Short

Jumper

Wire

Short

Jumper

Wire