Roberts Gorden Combat Cabinet Heaters POP-ECA/PGP-ECA 015 to 0100 User Manual

Page 28

Advertising
background image

COMBAT

®

C

ABINET

H

EATERS

I

NSTALLATION

, C

OMMISSIONING

, O

PERATION

AND

S

ERVICE

M

ANUAL

22

9.5 CCH Wiring Diagram Gas Models 15-30 (horizontal mounting)

Red

1

2

3

4

N

10 A

MAIN TERMINALS

IN CONTROL PANEL

Blue

Blue

Blue

L

L

L

1

2

3

PACKAGED
BURNER

FAN

LIMIT

FAN / LIMIT STAT

Brown

7

8

2

7

R1 COIL 240v

3

1

LOCKOUT SIGNAL

BURNER RUN SIGNAL

LOCKOUT RESET SIGNAL

5

6

REMOTE LOCKOUT
RESET

FOR BURNERS WITH
LANDIS & STEFA
CONTROL BOX
(GAS-FIRED)

N

REMOTE LOCKOUT
LAMP 230V

MAIN FAN
MOTOR

OUTPUTS
FROM
BURNER

TIME/TEMPERATURE

CONTROLS

FAN CONTROL
(OPTIONAL)

B4

S3

T2

T1

N

L1

B4

S3

T2

T1

N

L1

GAS BURNER 7-WAY PLUG

Re

d

/

W

hit

e

R

e

d /

W

hit

e

R

e

d /

W

hit

e

R

e

d /

W

hit

e

Re

d

R

e

d /

W

hit

e

Red / White

Red / White

Red / White

Red / White

Bl

u

e

230 V 50 Hz

1 PH SUPPLY

FOR GAS BURNER

T1 IS NOT USED

B4 = BURNER RUN TO R1 COIL

ALL OTHER WIRES SAME AS OIL

BURNER

1 mm2 Ø RED TRI RATED FLEX CABLE

NOTE:
Any of the original wire supplied with
the heater must be replaced with
wiring material having a temperature
rating of at least 105°C and 600 V.