Rheem Low NOX User Manual

Page 2

Advertising
background image

MODEL

INPUT

GPH

NUMBER

BTU/HR.

40°F

50°F 60°F 70°F 80°F

90°F 100°F 110°F 120°F 130°F 140°F

GN75-125

125,000

303

242

202

173

152

135

121

110

101

93

87

GN82-156

156,000

378

303

252

216

189

168

151

138

126

116

108

GN37-200

199,900

485

388

323

277

242

215

194

176

162

149

138

GN76-200

199,900

485

388

323

277

242

215

194

176

162

149

138

GN91-200

199,900

485

388

323

277

242

215

194

176

162

149

138

GN100-200(A)

199,900

485

388

323

277

242

215

194

176

162

149

138

GN72-250(A)

250,000

606

485

404

346

303

269

242

220

202

186

173

GN100-250(A)

250,000

606

485

404

346

303

269

242

220

202

186

173

GN100-270(A)

270,000

655

524

436

374

327

291

262

238

218

201

187

GN65-360(A)

360,000

873

698

582

499

436

388

349

317

291

269

249

GN100-400(A)

399,900

969

776

646

554

485

431

388

353

323

298

277

RECOVERY CAPACITIES

(80% thermal efficiency)

TEMP. RISE AT 100°F IN GALLONS

Min.

MODEL

TANK CAP.

INPUT

5

10

15

20

30

45

60

120

180

to Rec.

NUMBER

GALLONS

BTU/HR. Min. Min. Min. Min. Min. Min. Min. Min. Min. Contents

GN75-125

75

125,000

63

73

83

93

113

143

174

295

416

37

GN82-156

82

156,000

70

83

95

108

133

171

209

360

511

33

GN37-200

35

199,900

41

56

72

88

119

167

214

403

562

11

GN76-200

76

199,900

69

86

102

118

150

199

247

441

635

24

GN91-200

91

199,900

80

96

112

128

161

209

258

451

645

28

GN100-200(A)

100

199,900

86

102

118

135

167

215

264

458

652

31

GN72-250(A)

72

250,000

71

91

111

131

172

232

293

535

778

18

GN100-250(A)

100

250,000

90

110

131

151

191

252

312

555

797

25

GN100-270(A)

100

270,000

92

114

135

157

201

266

332

594

855

23

GN65-360(A)

65

360,000

75

104

133

162

220

307

395

744 1093

11

GN100-400(A)

100

399,900

102

135

167

199

264

361

458

846 1233

15

FIRST TIME DELIVERY

(Includes useable storage and recovery for indicated times.)

WATER CONNECTIONS

APPROXIMATE

MODEL

TOP

FRONT REAR

SHIPPING WEIGHT

NUMBER

A

B

C

D E F G H

IN/OUT

SIDE

SIDE

STD.

ASME

GN75-125

65-1/2

61

26-1/4

25

5

56

3/4

20

1-1/2

1-1/2

1-1/2

480 lbs.

N/A

GN82-156

68-13/16

64

26-1/4

25

6

58-5/8

3/4

20

1-1/2

1-1/2

1-1/2

490 lbs.

N/A

GN37-200

49-1/4

43-3/8

26-1/4

25

6

37-5/8

3/4

20

1-1/2

1-1/2

1-1/2

405 lbs.

N/A

GN76-200

68-13/16

64

26-1/4

25

6

58-5/8

3/4

20

1-1/2

1-1/2

1-1/2

540 lbs.

N/A

GN91-200

76-5/16

71-13/16

26-1/4

30-5/8

6

66-3/8

3/4

20

1-1/2

1-1/2

1-1/2

600 lbs.

N/A

GN100-200(A)

73-1/16

66-1/8

30-1/4

23-1/4

6

57-1/2

3/4

23

1-1/2

2

2

780 lbs.

835 lbs.

GN72-250(A)

71-1/16

64-1/2

26-1/4

25

6

58-5/8

3/4

20

1-1/2

1-1/2

1-1/2

590 lbs.

630 lbs.

GN100-250(A)

73-1/4

66-1/8

30-1/4

23-1/4

6

57-1/2

3/4

23

1-1/2

2

2

795 lbs.

835 lbs.

GN100-270(A)

73-7/8

66-1/8

30-1/4

23-1/4

6

57-1/2

3/4

23

1-1/2

2

2

805 lbs.

845 lbs.

GN65-360(A)

70-11/16

64-1/2

26-1/4

25

8

58-5/8

3/4

N/A

N/A

1-1/2

1-1/2

640 lbs.

680 lbs.

GN100-400(A)

76

68-1/2

30-1/4

32-1/4

8

61-3/4

1

23

1-1/2

2

2

770 lbs.

810 lbs.

DIMENSIONS

(Inches)

All Models Require a 120V /1.5 Amp Power Source. (A) Suffix Indicates ASME Tank Construction Available.

Recovery ratings are based on thermal efficiencies obtained in a CSA certified laboratory.
(A) indicates available ASME model.

Recommended specifications

(for trade reference only)

Water heater(s) shall be

UNIVERSAL

model ________________, manufactured by RHEEM-RUUD, having gas input of __________ Btu/hr. and a recovery rate of _____________ GPH at a

100°F temperature rise when tested and certified at ____________ thermal efficiency. Water heater(s) shall have a storage capacity of _________ gallons. Water heater(s) shall have the CSA
seal of certification and supplied with a factory installed AGA/ASME rated temperature and pressure relief valve. Tank(s) shall be furnished with a tube bundle having a double coating of high
temperature porcelain enamel and furnished with magnesium anode rods rigidly supported. Water heater(s) shall meet or exceed the thermal efficiency and standby loss requirements of
ASHRAE Standard 90.1b-2001. Tanks shall have a working pressure rating of 150 psi, and shall be completely factory assembled, including a pressure regulator properly adjusted for operation
on ___________ gas with stainless steel burners. Controls will be arranged for safety shutoff in event of pilot failure. Water heater(s) with
inputs less than 360,000 Btu/hr. shall have top, front and rear side inlet/outlet water connections. Water heater(s) shall be covered by a
three year limited warranty against tank leaks.

• Add for ASME construction –

Water heater(s) shall be constructed in accordance with the requirements of the ASME

Boiler and Pressure Vessel Code, Section IV Part HLW.

Limited Warranty

This product features a three year limited warranty against tank leaks. Please refer to Commercial Warranty Information brochure for
complete warranty information.

CLEARANCE TO
COMBUSTIBLES

(inches)

MODEL
NUMBER

SIDE

REAR TOP

GN75-125

2

2

12

GN82-156

2

2

12

GN37-200

2

2

12

GN76-200

2

2

12

GN91-200

2

2

12

GN100-200(A)

2

4

12

GN72-250(A)

6

6

12

GN100-250(A)

2

4

12

GN100-270(A)

2

4

12

GN65-360(A)

6

6

12

GN100-400(A)

6

6

12

C

H
E

A

B

F

D

OUTLET

TOP

INLET

TOP

OUTLET

FRONT SIDE

OUTLET

REAR SIDE

SYSTEM

SENTINEL

T&P

INLET

FRONT SIDE

INLET

REAR SIDE

G

7"

(178mm)

Rheem Water Heaters • 101 Bell Road, Montgomery, Alabama 36117-4305 • www.rheem.com

P R I N T E D I N U . S . A

0 5 / 0 7 W P

Form No. RR102C-1CA Rev. 3

In keeping with its policy of continuous progress and product improvement, Rheem-Ruud reserves the right to make changes without notice.

Advertising