Regency CLASSIC C34-2 Direct Vent Freestanding Gas Heater

INSTALLATION

EXTERIOR VENT TERMINAL LOCATIONS

*As specified in CGA B149 or ANZI 223.1 Installation Codes. Note: local Codes or Regulations may require different clearances.

**A vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves

both dwellings

***Only permitted if veranda, porch, deck or balcony, is fully open on a minimum of 2 sides beneath the floor.

A= Clearance above grade, veranda, porch, deck, or balcony

[*12" (30 cm) min.]

B= Clearance to window or door that may be opened [*12" (30cm)]

C= Clearance to permanently closed window min. 12" (30 cm)

D= Vertical clearance to ventilated soffit located above the terminal within a horizontal

distance of 24" (60 cm) from the centre-line of the terminal [18" (46 cm) min.]

E= Clearance to unventilated soffit [12" (30 cm) min.]

F=

Clearance to outside corner: with

AstroCap

Termination Cap (min 6"/15cm), with

Dura-Vent Termination Cap (12"/30cm)

G=

Clearance to inside corner: with

AstroCap

Termination Cap (min 6"/15cm), with Dura-

Vent Termination Cap (12"/30cm)

H= *Not to be installed above a meter/regulator assembly within 36"

(90 cm) horizontally from the centre-line of the regulator.

J=

clearance to service regulator vent outlet [*min. 36" (90cm)]

K= clearance to non-mechanical air supply inlet to building or

the combustion air inlet to any other appliance [*12 inches]

L= clearance to a mechanical air supply inlet [*min. 72" (1.8 m)

M= **clearance above paved side-walk or a paved driveway

located on public property [*84" (2.1 m) min.]

N=clearance under veranda, porch,, deck, or balcony [*12"

(30 cm) min.***]