Regency P121-1/P121LC-1/P121RC-1/P131-1 Zero Clearance Direct Vent Gas Fireplace

19

INSTALLATION

Vertical Venting with Two (2) 90

o

Elbows

Option

V

+

V1

H

A)

1' (305mm) Minimum

4' (1.22m) Maximum

B)

2' (610mm) Minimum

6' (1.86m) Maximum

C)

3' (914mm) Minimum

9' (2.7m) Maximum

D)

4' (1.22m) Minimum

12' (3.6m) Maximum

E)

5' (1.5m) Minimum

15' (4.5m) Maximum

F)

6' (1.86m) Minimum

17' (5.1m) Maximum

Vertical Venting with Two (2) 90

o

Elbows

Vertical Venting with Three (3) 90

o

Elbows

Diagram 9

Diagram 10

Diagram 11

Option

V

H + H1

A)

1' (305mm) Minimum

2' (610mm) Maximum

B)

2' (610mm) Minimum

4' (1.22m) Maximum

C)

3' (914mm) Minimum

6' (1.86m) Maximum

D)

4' (1.22m) Minimum

8' (2.4m) Maximum

With the above options, maximum total pipe length if 37 feet with mini-
mum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90

o

elbows is required.

With the above options, maximum total pipe length if 37 feet with mini-
mum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90

o

elbows is required.

Option

V + V1 H

H + H1

A)

2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max.

B)

3' (914mm) Min. 4' (1.22m) Max. 5' (1.5m) Max.

C)

4' (1.22mm) Min. 6' (1.86m) Max. 8' (2.4m) Max.

D)

5' (1.5m) Min.

8' (2.4m) Max.

12' (3.6m) Max.

With the above options, maximum total pipe length if 37 feet with mini-
mum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90

o

elbows is required.